{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"5SL6206-8CC","brand":"Siemens","brandSlug":"siemens","productSlug":"5SL6206-8CC","canonicalUrl":"https://aoctrl.com/siemens/5SL6206-8CC","factsUrl":"https://aoctrl.com/api/mcp/products/5SL6206-8CC","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 5SL6206-8CC, miniature circuit breaker, 2-pole, D-curve, 6 A, 400 V AC, 6 kA breaking capacity per EN 60898, 2 MWU, IP20.","salesMarkdown":"The Siemens 5SL6206-8CC is a SENTRON miniature circuit breaker (MCB) — a 2-pole, D-curve unit rated 6 A at 400 V AC, with a 6 kA breaking capacity tested to EN 60898. The 400 V AC rated voltage covers 3-phase line-to-line supplies up to 440 V maximum in multi-phase operation. The 6 A rating is the continuous thermal current — the breaker will carry 6 A indefinitely at 30 °C ambient without nuisance tripping, and the D-curve's magnetic trip kicks in above 60–120 A for short-circuit events. ## Where it goes — deployment context Suitability for operation in residential buildings and infrastructure is the manufacturer's stated application field — think consumer units, sub-distribution boards, lighting panels, and small commercial DBs. The D-curve makes it a natural fit for motor circuits (pumps, fans, compressors) and small transformers where the inrush would trip a B- or C-curve breaker on energization. Mounting position is unrestricted, so it can be installed horizontally or vertically in a panel. The sealable design allows a lead seal or lock to prevent unauthorized operation — useful for utility-metered or shared-access boards. Supplementary devices like shunt trips, auxiliary contacts, or alarm switches can be added via the SENTRON accessory range. ## How it compares to nearby siblings The closest peer in the ledger is the 5SL4363-7 — a 3-pole, C-curve, 63 A breaker with a 10 kA breaking capacity per both EN 60898 and IEC 60947-2. The 5SL6206-8CC shares the same 76 mm depth, 90 mm height, and SENTRON platform, but at 36 mm wide (2 MWU) versus 54 mm wide (3 MWU). The D-curve on the 6 A unit is the key difference: the 5SL4363-7's C-curve is for general-purpose loads, while the D-curve here is specifically for high-inrush applications.","metaTitle":"Siemens 5SL6206-8CC SENTRON MCB, 2P D 6A 400V 6kA","metaDescription":"Siemens 5SL6206-8CC SENTRON miniature circuit breaker, 2-pole, D-curve, 6 A, 400 V AC, 6 kA breaking capacity per EN 60898. Active production, available to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":[],"specifications":{"Depth":"76 mm","Poles":"2","Width":"36 mm","Height":"90 mm","IP Rating":"IP20","Product Status":"Active"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/11ee2dc4c1cacb91e4cc204c5ea1e4d7.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=258287&mlfb=5SL6206-8CC","alternativesUrl":"https://aoctrl.com/api/mcp/products/5SL6206-8CC/alternatives.json"},"ai":{"faq":[],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/5SL6206-8CC","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/5SL6206-8CC when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}