{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"5SL6225-7","brand":"Siemens","brandSlug":"siemens","productSlug":"5SL6225-7","canonicalUrl":"https://aoctrl.com/siemens/5SL6225-7","factsUrl":"https://aoctrl.com/api/mcp/products/5SL6225-7","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 5SL6225-7 miniature circuit breaker, 2-pole, C-curve, 25 A, 6 kA breaking capacity at 400 V AC, 2 MW units wide.","salesMarkdown":"## What this 5SL6225-7 is and what the ratings mean The Siemens 5SL6225-7 is a SENTRON miniature circuit breaker (MCB) — a 2-pole unit with a C tripping characteristic, rated 25 A, and a 6 kA breaking capacity at 400 V AC. That 6 kA figure applies per both EN 60898 and IEC 60947-2, so it's certified for residential and light commercial distribution boards where the prospective short-circuit current stays under that threshold. The C-curve means it trips between 5 and 10 times rated current — standard for general-purpose loads like lighting, socket circuits, and small appliances where you don't want nuisance trips from inrush but still need fast clearing on a hard fault. At 36 mm wide (2 modular width units), it snaps onto a standard DIN rail and occupies two slots in a distribution board. The 76 mm depth and 70 mm installation depth keep it flush with other SENTRON 5SL series breakers, so it fits existing enclosures without re-spacing. Mounting position is any — no derating needed for horizontal or inverted orientation, which simplifies panel layout. Power loss per pole is 2.6 W at rated current in hot operating state — useful to know for thermal budgeting inside a sealed enclosure. The breaker is sealable (tamper-evident cover available), halogen-free and silicon-free, which matters for installations with sensitive contacts or where off-gassing during a fault must be minimized. ## Where it fits in the panel Rated for overvoltage category III and pollution degree 2 — that's the standard for fixed-installation distribution boards inside a building envelope. The IP20 rating (with connected conductors) means it's protected against finger contact but not against water ingress; it belongs inside a cabinet, not in a washdown zone. Operating temperature range is -40 °C to 75 °C, so it handles unheated utility rooms or outdoor enclosures in temperate climates.","metaTitle":"Siemens 5SL6225-7 SENTRON MCB, 2P C 25A 6kA","metaDescription":"Siemens 5SL6225-7 SENTRON miniature circuit breaker, 2-pole, C-curve, 25 A, 6 kA breaking capacity per IEC 60898/60947-2. Active production, sourced to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":[],"specifications":{"Depth":"76 mm","Poles":"2","Width":"36 mm","Height":"90 mm","IP Rating":"IP20","Product Status":"Active","Energy Limitation Class":"3"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/271a7262e60aa92c66d3dffe83109b41.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=442270&mlfb=5SL6225-7","alternativesUrl":"https://aoctrl.com/api/mcp/products/5SL6225-7/alternatives.json"},"ai":{"faq":[],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/5SL6225-7","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/5SL6225-7 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}