{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"5SL6225-7CC","brand":"Siemens","brandSlug":"siemens","productSlug":"5SL6225-7CC","canonicalUrl":"https://aoctrl.com/siemens/5SL6225-7CC","factsUrl":"https://aoctrl.com/api/mcp/products/5SL6225-7CC","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 5SL6225-7CC miniature circuit breaker, 2-pole, C-curve, 25 A rated, 6 kA breaking capacity per EN 60898, 400 V AC.","salesMarkdown":"Siemens 5SL6225-7CC is a 2-pole SENTRON miniature circuit breaker with a C tripping characteristic, rated 25 A at 400 V AC and a 6 kA breaking capacity per EN 60898. Derate to 23.58 A at 40 °C, 22.83 A at 45 °C, 22.06 A at 50 °C, and 21.26 A at 55 °C — so if your panel runs hot, size for the derated figure, not the nameplate. Pollution degree 2 covers normal non-condensing environments. ## Panel fit and environmental range Overall dimensions: 90 mm high, 36 mm wide (2 MW), 76 mm deep; installation depth is 70 mm. IP20 with connected conductors — fine inside an enclosure, not for wet locations. Designed to EN 60898 for overcurrent protection. The SENTRON series carries CE marking and is RoHS-compliant by declaration. For specific UL, REACH, or IEC 60947-2 documentation, request the manufacturer's declaration package at quote time — it's not pre-loaded in the listing but is available through the supply channel.","metaTitle":"Siemens 5SL6225-7CC SENTRON MCB, 25A 2P C-curve, 6kA","metaDescription":"Siemens 5SL6225-7CC SENTRON miniature circuit breaker, 25A, 2-pole, C characteristic, 6kA breaking capacity per EN 60898. Active production. Order against RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["2-Pole MCB (DIN Rail)"],"specifications":{"Depth":"76 mm","Width":"36 mm","title":"5SL6225-7CC","Height":"90 mm","Maximum":"75 °C","Minimum":"-40 °C","Sealable":"Yes","description":"Miniature circuit breaker 400 V 6kA, 2-pole, C, 25A Circuit breaker 400 V 6kA, 2-pole, C, 25A","Halogen-Free":"Yes","Silicon-Free":"Yes","Design Of Pole":"2P","Number Of Poles":"2","lifecycle_stage":"current","Mounting Position":"any","Installation Depth":"70 mm","Product Brand Name":"SENTRON","Degree Of Pollution":"2","Product Designation":"Miniature circuit breaker","at AC / rated value":"25 A","protection class IP":"IP20, with connected conductors","Overvoltage Category":"III","Energy Limitation Class":"3","according to EN 61346-2":"F","at 30 °C / rated value":"25 A","at 40 °C / rated value":"23.58 A","at 45 °C / rated value":"22.83 A","at 50 °C / rated value":"22.06 A","at 55 °C / rated value":"21.26 A","according to IEC 81346-2":"F","Suitability For Operation":"Residential buildings/infrastructure","Number Of Modular Width Units":"2","Tripping Characteristic Class":"C","at DC / rated value / maximum":"72 V","according to EN 60898 / rated value":"6 kA","supply voltage / at AC / rated value":"400 V","Type Of Voltage / Of The Operating Voltage":"AC","with multi-phase operation / at AC / maximum":"440 V","Value Range / Of The Supply Voltage Frequency":"50/60 Hz","with multi-phase operation / at AC / rated value":"440 V","vibration resistance / according to IEC 60068-2-6":"50 m/s² at 25 to 150 Hz"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"stockQuantity":0,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/271a7262e60aa92c66d3dffe83109b41.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=359384&mlfb=5SL6225-7CC"},"ai":{"faq":[{"question":"What is 5SL6225-7CC's width and depth?","answer":"Width is 36 mm (2 modular units), depth is 76 mm, installation depth is 70 mm."},{"question":"Where can I buy 5SL6225-7CC?","answer":"Sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing confirmed at quote time."},{"question":"What compliance documentation does Siemens provide for 5SL6225-7CC?","answer":"The part carries CE marking and is designed to EN 60898. RoHS compliance is by declaration. For UL, REACH, or IEC 60947-2 documentation, request the manufacturer's declaration package at quote time."},{"question":"Will 5SL6225-7CC drop into a panel specified around 5SL4106-7CC?","answer":"Both are 2-pole SENTRON MCBs on the same DIN-rail footprint, but 5SL4106-7CC is a 6 A B-curve unit. The 5SL6225-7CC is 25 A C-curve — same physical fit, different protection profile. No rewiring needed if the busbar and load match the higher rating."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"icboms-matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/5SL6225-7CC","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/5SL6225-7CC when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-08-11T15:51:03.652Z","lastPublished":"2026-08-11T15:51:03.652Z","indexable":true}}