{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"5SL6232-7","brand":"Siemens","brandSlug":"siemens","productSlug":"5SL6232-7","canonicalUrl":"https://aoctrl.com/siemens/5SL6232-7","factsUrl":"https://aoctrl.com/api/mcp/products/5SL6232-7","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 5SL6232-7, miniature circuit breaker, 2-pole, C characteristic, 32 A rated, 6 kA breaking capacity at 400 V AC, 50/60 Hz.","salesMarkdown":"It breaks fault currents up to 6 kA per both EN 60898 and IEC 60947-2 at 400 V AC, 50/60 Hz. Full rated current is 32 A at 30 °C. At 40 °C it's 30.06 A, at 45 °C it's 29.44 A, and at 55 °C it's 26.89 A — so if your panel runs warm, size the load accordingly. For a 2-pole breaker that's 6.2 W total — small enough to ignore in a thermal budget for most enclosures, but worth noting if you're packing a dense row of breakers. Mounts in any position on standard DIN rail. Sealable, halogen-free, silicon-free. Overvoltage category III, pollution degree 2. Supplementary devices can be installed on the side.","metaTitle":"Siemens 5SL6232-7 SENTRON MCB, 2P C-32A 6kA, 400V","metaDescription":"Siemens 5SL6232-7 SENTRON miniature circuit breaker, 2-pole, C-curve 32 A, 6 kA breaking capacity per IEC 60898 and IEC 60947-2. Active production, available to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["2-Pole MCB (DIN Rail)"],"specifications":{"Depth":"76 mm","Width":"36 mm","Height":"90 mm","Maximum":"75 °C","Minimum":"-40 °C","Sealable":"Yes","Halogen-Free":"Yes","Silicon-Free":"Yes","Design Of Pole":"2P","Number Of Poles":"2","lifecycle_stage":"current","Mounting Position":"any","at AC rated value":"32 A","Installation Depth":"70 mm","Product Brand Name":"SENTRON","Degree Of Pollution":"2","Product Designation":"Miniature circuit breaker","protection class IP":"IP20, with connected conductors","Overvoltage Category":"III","at 30 °C rated value":"32 A","at 40 °C rated value":"30.06 A","at 45 °C rated value":"29.44 A","at 55 °C rated value":"26.89 A","Energy Limitation Class":"3","Suitability For Operation":"Residential buildings/infrastructure","at DC rated value maximum":"72 V","Number Of Modular Width Units":"2","Tripping Characteristic Class":"C","supply voltage at AC rated value":"400 V","according to EN 60898 rated value":"6 kA","according to IEC 60947-2 rated value":"6 kA","Type Of Voltage Of The Operating Voltage":"AC","with multi-phase operation at AC maximum":"440 V","Value Range Of The Supply Voltage Frequency":"50/60 Hz","with multi-phase operation at AC rated value":"440 V","Mechanical Service Life (Operating Cycles) Typical":"10 000","Product Extension Installable Supplementary Devices":"Yes","power loss [W] for rated value of the current at AC in hot operating state per pole":"3.1 W"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/397f4b2b56a52cefae2fd3956c626244.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=407329&mlfb=5SL6232-7","alternativesUrl":"https://aoctrl.com/api/mcp/products/5SL6232-7/alternatives.json"},"ai":{"faq":[{"question":"What is the breaking capacity of 5SL6232-7?","answer":"6 kA per both EN 60898 and IEC 60947-2 at 400 V AC. That's the same figure under both standards, so it's a solid fit for residential and light commercial distribution boards."},{"question":"Where can I buy 5SL6232-7?","answer":"It's sourced to order against an RFQ through independent distribution channels. Availability and current pricing are confirmed at quote time."},{"question":"What compliance documentation is available for 5SL6232-7?","answer":"The breaker carries ratings per EN 60898 and IEC 60947-2. It is halogen-free and silicon-free. For specific RoHS, REACH, or UL documentation, request it with your RFQ."},{"question":"Will 5SL6232-7 drop into a panel specified for 5SL4363-7?","answer":"Both are 2-pole SENTRON MCBs with the same 36 mm width and DIN-rail mounting, so they share the same footprint and rail clip. The difference is in the rating — verify the load current and breaking capacity match your panel design before swapping."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/5SL6232-7","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/5SL6232-7 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}