{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"5SL6313-7","brand":"Siemens","brandSlug":"siemens","productSlug":"5SL6313-7","canonicalUrl":"https://aoctrl.com/siemens/5SL6313-7","factsUrl":"https://aoctrl.com/api/mcp/products/5SL6313-7","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 5SL6313-7 miniature circuit breaker, 3-pole, C-curve, 13 A, 400 V AC, 6 kA breaking capacity per EN 60898 / IEC 60947-2.","salesMarkdown":"It breaks fault currents up to 6 kA per EN 60898 and IEC 60947-2 at 400 V AC — the standard interrupting rating for residential and light-commercial distribution boards in 50/60 Hz networks. Depth is 76 mm (70 mm installation depth), which fits flush in most 85 mm deep distribution enclosures. Sealable terminals allow the installer to lock the cover after commissioning, a requirement in some utility-metered installations. The closest peer in the same form factor is the 5SL4363-7 — identical dimensions (76×54×90 mm), same 3-pole C-curve 13 A rating, same 400 V AC / 440 V max, same 10 000 mechanical cycles, same sealable terminals. The difference is breaking capacity: the 5SL4363-7 carries a 10 kA rating per both EN 60898 and IEC 60947-2, versus 6 kA on this part. If the panel's prospective short-circuit current (PSCC) at the breaker's location is under 6 kA, the 5SL6313-7 is the correct fit. For a board fed close to a transformer where fault levels exceed 6 kA, step up to the 5SL4363-7. No wiring or busbar changes needed — same footprint, same DIN-rail clip. Halogen-free and silicon-free construction — important for installations where off-gassing during a fault must not corrode adjacent contacts or sensitive electronics.","metaTitle":"Siemens 5SL6313-7 SENTRON MCB, 3P C 13A, 6kA","metaDescription":"Siemens 5SL6313-7 SENTRON miniature circuit breaker, 3-pole, C-curve, 13A, 400V AC, 6kA breaking capacity per EN 60898. Active production. Order to RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Miniature Circuit Breakers (MCB)"],"specifications":{"Depth":"76 mm","Width":"54 mm","Height":"90 mm","Maximum":"75 °C","Minimum":"-40 °C","Sealable":"Yes","Halogen-Free":"Yes","Silicon-Free":"Yes","Design Of Pole":"3P","Number Of Poles":"3","lifecycle_stage":"current","Mounting Position":"any","Installation Depth":"70 mm","Product Brand Name":"SENTRON","Degree Of Pollution":"2","Product Designation":"Miniature circuit breaker","protection class IP":"IP20, with connected conductors","Overvoltage Category":"III","Energy Limitation Class":"3","Suitability For Operation":"Residential buildings/infrastructure","at DC rated value maximum":"72 V","Number Of Modular Width Units":"3","Tripping Characteristic Class":"C","supply voltage at AC rated value":"400 V","according to EN 60898 rated value":"6 kA","according to IEC 60947-2 rated value":"6 kA","Type Of Voltage Of The Operating Voltage":"AC","with multi-phase operation at AC maximum":"440 V","Value Range Of The Supply Voltage Frequency":"50/60 Hz","with multi-phase operation at AC rated value":"440 V","Mechanical Service Life (Operating Cycles) Typical":"10 000","Product Extension Installable Supplementary Devices":"Yes","power loss [W] for rated value of the current at AC in hot operating state per pole":"1.9 W"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/95847b114b9ce37bd2cdcd21fa7fe82f.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=515957&mlfb=5SL6313-7","alternativesUrl":"https://aoctrl.com/api/mcp/products/5SL6313-7/alternatives.json"},"ai":{"faq":[{"question":"Will 5SL6313-7 drop into a panel specified around 5SL4363-7 without rewiring?","answer":"Yes. Both breakers share the same 76 mm depth, 54 mm width (3 MW), 90 mm height, DIN-rail clip, and 3-pole C-curve 13 A rating. The only difference is breaking capacity — 6 kA on the 5SL6313-7 versus 10 kA on the 5SL4363-7. If the panel's fault level is ≤6 kA, the swap is mechanical and electrical drop-in; no busbar or wiring changes needed."},{"question":"Where can I buy the 5SL6313-7?","answer":"The 5SL6313-7 is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time — submit an RFQ for a firm price and delivery estimate."},{"question":"What compliance documentation does Siemens provide for the 5SL6313-7?","answer":"The 5SL6313-7 is rated per EN 60898 and IEC 60947-2 for breaking capacity. It carries an IP20 protection class (with conductors connected), pollution degree 2, and overvoltage category III. The construction is halogen-free and silicon-free. Siemens typically provides a declaration of conformity covering CE, UKCA, and EAC for the SENTRON series; specific certificates (UL, CSA) are not listed in the available spec data for this order code."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/5SL6313-7","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/5SL6313-7 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}