{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"5SL6332-6CC","brand":"Siemens","brandSlug":"siemens","productSlug":"5SL6332-6CC","canonicalUrl":"https://aoctrl.com/siemens/5SL6332-6CC","factsUrl":"https://aoctrl.com/api/mcp/products/5SL6332-6CC","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 5SL6332-6CC miniature circuit breaker, 3-pole, B characteristic, 32 A rated current, 400 V AC, 6 kA breaking capacity per EN 60898.","salesMarkdown":"The Siemens SENTRON 5SL6332-6CC is a 3-pole miniature circuit breaker (MCB) with a B tripping characteristic, rated 32 A at 400 V AC and a breaking capacity of 6 kA according to EN 60898. The 6 kA breaking capacity at 400 V tells you it can safely interrupt a fault current up to 6,000 A without welding contacts or cascading failure upstream — adequate for most final subcircuits in a TN or TT system where the prospective short-circuit current stays under that threshold. Rated for 50/60 Hz supply, the 5SL6332-6CC accepts up to 440 V AC in multi-phase operation. Width is 54 mm — that's 3 modular width units at 18 mm each, so it occupies three adjacent slots in the distribution board. Depth is 76 mm, installation depth 70 mm; the 90 mm height leaves clearance for most enclosure lids with busbar shrouds. Mounting position is any, which simplifies layout in crowded panels. Sealable design allows tamper-proofing with a lead seal wire through the housing. Vibration resistance tested to 50 m/s² at 25 to 150 Hz per IEC 60068-2-6 — it holds up on machine-mounted sub-distribution near pumps or conveyors.","metaTitle":"Siemens SENTRON 5SL6332-6CC MCB, 3P, B Curve, 32 A, 6 kA","metaDescription":"Siemens SENTRON 5SL6332-6CC miniature circuit breaker. 3-pole, B characteristic, 32 A, 400 V AC, 6 kA breaking capacity per EN 60898. Active production. Sourced to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["3-Pole MCB (DIN Rail)"],"specifications":{"Depth":"76 mm","Width":"54 mm","title":"5SL6332-6CC","Height":"90 mm","Maximum":"75 °C","Minimum":"-40 °C","Sealable":"Yes","description":"Miniature circuit breaker 400 V 6kA, 3-pole, B, 32 A Circuit breaker 400 V 6kA, 3-pole, B, 32 A","Halogen-Free":"Yes","Silicon-Free":"Yes","Design Of Pole":"3P","Number Of Poles":"3","lifecycle_stage":"current","Mounting Position":"any","Installation Depth":"70 mm","Product Brand Name":"SENTRON","Degree Of Pollution":"2","Product Designation":"Miniature circuit breaker","protection class IP":"IP20, with connected conductors","Overvoltage Category":"III","Energy Limitation Class":"3","Suitability For Operation":"Residential buildings/infrastructure","at DC rated value maximum":"72 V","Number Of Modular Width Units":"3","Tripping Characteristic Class":"B","supply voltage at AC rated value":"400 V","according to EN 60898 rated value":"6 kA","Type Of Voltage Of The Operating Voltage":"AC","with multi-phase operation at AC maximum":"440 V","Value Range Of The Supply Voltage Frequency":"50/60 Hz","with multi-phase operation at AC rated value":"440 V","vibration resistance according to IEC 60068-2-6":"50 m/s² at 25 to 150 Hz","Product Extension Installable Supplementary Devices":"Yes","power loss [W] for rated value of the current at AC in hot operating state per pole":"4.6 W"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"stockQuantity":0,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/c6464c67136c5b0165c8417af47a0439.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=432534&mlfb=5SL6332-6CC"},"ai":{"faq":[{"question":"Will 5SL6332-6CC drop into a panel specified around 5SL4363-7 without rewiring?","answer":"Yes — the two share the same physical footprint (54 mm width, 76 mm depth, 90 mm height), same DIN-rail mounting, and same 3-pole busbar pitch. No enclosure modification or rewiring is needed for the swap. The only change is the tripping curve (B vs C) and the breaking capacity rating, which affects coordination with upstream devices, not the physical fit."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"icboms-matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/5SL6332-6CC","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/5SL6332-6CC when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-08-11T15:51:03.652Z","lastPublished":"2026-08-11T15:51:03.652Z","indexable":true}}