{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"5SL6332-7CC","brand":"Siemens","brandSlug":"siemens","productSlug":"5SL6332-7CC","canonicalUrl":"https://aoctrl.com/siemens/5SL6332-7CC","factsUrl":"https://aoctrl.com/api/mcp/products/5SL6332-7CC","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 5SL6332-7CC, 3-pole miniature circuit breaker, C-curve, 32 A rated current, 400 V AC, 6 kA breaking capacity per EN 60898.","salesMarkdown":"The Siemens 5SL6332-7CC is a SENTRON miniature circuit breaker (MCB) in a 3-pole configuration with a C tripping characteristic, rated at 32 A and 400 V AC. It provides a 6 kA breaking capacity according to EN 60898, making it suitable for protecting branch circuits in residential and light commercial infrastructure panels where the prospective short-circuit current stays under that threshold. ## What the ratings mean for fit The C-curve (tripping between 5 and 10 times rated current) handles moderate inrush from motorized loads like pumps or small compressors without nuisance tripping — a common choice for mixed resistive-inductive circuits in distribution boards. The 6 kA breaking capacity at 400 V AC is the maximum fault current this MCB can safely interrupt; verify that the available fault current at the installation point does not exceed this value to maintain coordination with upstream devices. The 3-pole design covers three-phase loads or three single-phase circuits sharing a neutral. Rated operational voltage extends to 440 V AC maximum in multi-phase operation, which covers standard 400 V three-phase networks across 50/60 Hz supplies. Physical fit is defined by the 3-module-width footprint (54 mm wide, 90 mm tall, 76 mm deep) with a 70 mm installation depth behind the panel. It snaps onto standard DIN rail and accepts supplementary devices (auxiliary contacts, shunt trips, alarm switches) via the accessory slot — useful for remote status monitoring or emergency shutdown integration. ## Integration notes Mounts in any position on 35 mm DIN rail. The IP20 rating (with connected conductors) means it is intended for enclosed distribution boards — not for wet or dust-exposed locations. Pollution degree 2 and overvoltage category III are standard for fixed-installation MCBs in residential and commercial panels. Operating temperature range spans -40 °C to 75 °C, which covers most indoor and sheltered outdoor enclosures. Power dissipation per pole at rated current is 4.6 W in hot operating state. For a 3-pole unit that totals about 13.8 W — factor this into the enclosure thermal budget, especially in high-density DIN-rail layouts where adjacent breakers share the same air volume. Halogen-free and silicon-free construction reduces corrosive off-gassing risk in enclosed panels, which matters for sensitive electronics sharing the same enclosure.","metaTitle":"Siemens 5SL6332-7CC SENTRON MCB, 3P C 32 A 6 kA","metaDescription":"Siemens 5SL6332-7CC SENTRON miniature circuit breaker, 3-pole, C-curve, 32 A, 400 V AC, 6 kA breaking capacity per EN 60898. Active production, available to order against RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["3-Pole MCB (DIN Rail)"],"specifications":{"Depth":"76 mm","Width":"54 mm","title":"5SL6332-7CC","Height":"90 mm","Maximum":"75 °C","Minimum":"-40 °C","Sealable":"Yes","description":"Miniature circuit breaker 400 V 6kA, 3-pole, C, 32 A Circuit breaker 400 V 6kA, 3-pole, C, 32 A","Halogen-Free":"Yes","Silicon-Free":"Yes","Design Of Pole":"3P","Number Of Poles":"3","lifecycle_stage":"current","Mounting Position":"any","Installation Depth":"70 mm","Product Brand Name":"SENTRON","Degree Of Pollution":"2","Product Designation":"Miniature circuit breaker","protection class IP":"IP20, with connected conductors","Overvoltage Category":"III","Energy Limitation Class":"3","Suitability For Operation":"Residential buildings/infrastructure","at DC rated value maximum":"72 V","Number Of Modular Width Units":"3","Tripping Characteristic Class":"C","supply voltage at AC rated value":"400 V","according to EN 60898 rated value":"6 kA","Type Of Voltage Of The Operating Voltage":"AC","with multi-phase operation at AC maximum":"440 V","Value Range Of The Supply Voltage Frequency":"50/60 Hz","with multi-phase operation at AC rated value":"440 V","vibration resistance according to IEC 60068-2-6":"50 m/s² at 25 to 150 Hz","Product Extension Installable Supplementary Devices":"Yes","power loss [W] for rated value of the current at AC in hot operating state per pole":"4.6 W"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"stockQuantity":0,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/e499850521235bd260832470109c133c.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=414278&mlfb=5SL6332-7CC"},"ai":{"faq":[{"question":"Where can I buy 5SL6332-7CC and how do I get a price?","answer":"The 5SL6332-7CC is sourced to order through independent distribution. Submit an RFQ for current availability and pricing — confirmed at quote time, not from a live stock feed."},{"question":"Will 5SL6332-7CC drop into a panel specified around 5SL4363-7 without rewiring?","answer":"Yes, the two share identical dimensions (76 mm depth, 54 mm width, 90 mm height) and the same 3-pole C-curve DIN-rail footprint. The main difference is breaking capacity: the 5SL4363-7 is rated 10 kA per EN 60898 and IEC 60947-2, versus 6 kA for the 5SL6332-7CC. If the available fault current at the panel is under 6 kA, the 5SL6332-7CC is a drop-in mechanical fit with no rewiring needed."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"icboms-matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/5SL6332-7CC","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/5SL6332-7CC when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-08-11T15:51:03.652Z","lastPublished":"2026-08-11T15:51:03.652Z","indexable":true}}