{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"5SL6413-7","brand":"Siemens","brandSlug":"siemens","productSlug":"5SL6413-7","canonicalUrl":"https://aoctrl.com/siemens/5SL6413-7","factsUrl":"https://aoctrl.com/api/mcp/products/5SL6413-7","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 5SL6413-7, miniature circuit breaker, 4-pole, C-curve, 13 A rated at 30 °C, 6 kA breaking capacity, 400 V AC.","salesMarkdown":"## What the ratings mean for your panel The Siemens 5SL6413-7 is a SENTRON 4-pole miniature circuit breaker with a C-curve tripping characteristic, rated 13 A at 30 °C and 6 kA breaking capacity per both EN 60898 and IEC 60947-2. The C-curve means it trips between 5 and 10 times rated current — standard for motor and transformer inrush where you need a bit of headroom over a B-curve but still protect branch wiring. The 6 kA rating tells you it can safely interrupt a fault up to that level without upstream coordination issues in a typical residential or light commercial distribution board. Rated voltage is 400 V AC, so it handles three-phase 4-wire supplies common in European infrastructure panels. ## Mounting and integration Mounts on standard DIN rail in any position. At 4 modular width units (72 mm wide), it takes four 18 mm slots in the distribution board. Depth is 76 mm (70 mm installation depth behind the panel face), so it fits flush in most consumer units and sub-distribution enclosures. IP20 with connected conductors — fine for dry indoor panels; not rated for washdown or outdoor exposure. Sealable terminals allow lockout-tagout compliance. Halogen-free and silicon-free construction meets low-smoke, zero-halogen material specs for public-building installations. ## Derating and ambient conditions Rated 13 A at 30 °C; derates to 12.37 A at 40 °C and 11.36 A at 55 °C. If your panel runs hot — say, a crowded enclosure near a furnace or in a rooftop cabinet — use the 40 °C figure for sizing. Ambient range is -40 to 75 °C operating, with periodic 95% humidity at 55 °C. Pollution degree 2 (normal, non-condensing) and overvoltage category III (fixed installation, distribution level).","metaTitle":"Siemens 5SL6413-7 SENTRON MCB, 4P C-Curve 13 A 6 kA","metaDescription":"Siemens 5SL6413-7 SENTRON miniature circuit breaker, 4-pole, C-curve, 13 A, 6 kA breaking capacity per IEC 60898 / IEC 60947-2. Active production, sourced to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["4-Pole MCB (DIN Rail)"],"specifications":{"Depth":"76 mm","Width":"72 mm","title":"5SL6413-7","Height":"90 mm","Maximum":"75 °C","Minimum":"-40 °C","Sealable":"Yes","description":"Miniature circuit breaker 400 V 6kA, 4-pole, C, 13A","Halogen-Free":"Yes","Silicon-Free":"Yes","Number Of Poles":"4","Type Of Voltage":"AC","lifecycle_stage":"current","Mounting Position":"any","Installation Depth":"70 mm","Product Brand Name":"SENTRON","Degree Of Pollution":"2","Product Designation":"Miniature circuit breaker","acc. to IEC 81346-2":"F","at AC / rated value":"13 A","protection class IP":"IP20, with connected conductors","Overvoltage Category":"III","Number Of Poles / Note":"4P","acc. to DIN EN 61346-2":"F","Energy Limitation Class":"3","at 30 °C / rated value":"13 A","at 40 °C / rated value":"12.37 A","at 45 °C / rated value":"11.96 A","at 55 °C / rated value":"11.36 A","Suitability For Operation":"Residential buildings/infrastructure","Number Of Modular Width Units":"4","Tripping Characteristic Class":"C","at DC / rated value / maximum":"72 V","acc. to EN 60898 / rated value":"6 kA","acc. to IEC 60947-2 / rated value":"6 kA","Product Feature / Touch Protection":"Yes","supply voltage / at AC / rated value":"400 V","Influence Of The Surrounding Temperature":"Periodically +55°C, max. 95% humidity","with multi-phase operation / at AC / maximum":"440 V","Product Function / Neutral Conductor Switching":"No","with multi-phase operation / at AC / rated value":"440 V","Mechanical Service Life (Operating Cycles) / Typical":"10 000"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"stockQuantity":0,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/7891f742c99c05f4bec13b9ca563b8c9.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=141792&mlfb=5SL6413-7"},"ai":{"faq":[{"question":"What is the breaking capacity of 5SL6413-7?","answer":"6 kA per both EN 60898 and IEC 60947-2. That's the standard for residential and light commercial distribution boards; for higher fault levels you'd step up to an SENTRON 3VA or similar."},{"question":"Where can I buy 5SL6413-7 and how is it quoted?","answer":"Sourced to order through independent distribution. Submit an RFQ for current pricing and availability — confirmed at quote time. Volume pricing negotiable."},{"question":"What does the C-curve mean on this breaker?","answer":"Trips between 5 and 10 times rated current (65–130 A for this 13 A unit). Designed for circuits with moderate inrush — motor starters, transformers, lighting banks — where a B-curve would nuisance-trip but a D-curve would protect too slowly."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"icboms-matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/5SL6413-7","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/5SL6413-7 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-08-11T15:51:03.652Z","lastPublished":"2026-08-11T15:51:03.652Z","indexable":true}}