{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"5SL6501-8CC","brand":"Siemens","brandSlug":"siemens","productSlug":"5SL6501-8CC","canonicalUrl":"https://aoctrl.com/siemens/5SL6501-8CC","factsUrl":"https://aoctrl.com/api/mcp/products/5SL6501-8CC","rawCanonicalId":null},"summary":{"shortDescription":"Siemens 5SL6501-8CC, miniature circuit breaker, 230 V, 6 kA, 1+N-pole, D characteristic, 1 A.","salesMarkdown":"The 1+N-pole configuration switches both the phase and neutral, with overcurrent protection on the phase only; the neutral pole is a switching pole without overload protection, common in single-phase final subcircuits where disconnection of both conductors is required. RoHS compliance is confirmed since June 2013, and REACH candidate-list information is available from the manufacturer. No UL or CSA listing appears in the record; verify local code acceptance for your jurisdiction. The 1 A rating and D-curve make this a niche selection: it protects a very low-current circuit against short-circuit and overload, while tolerating the high inrush of a small motor or transformer. A standard C-curve 1 A breaker would nuisance-trip on the same load. ## Integration notes Mounts on standard DIN rail. The 1+N width occupies two modular spaces. The D-curve magnetic trip operates at 10–20 times In (10–20 A), so coordination with upstream devices should account for this higher let-through energy during a fault.","metaTitle":"Siemens 5SL6501-8CC Miniature Circuit Breaker 230V 6kA 1+N D","metaDescription":"Siemens 5SL6501-8CC miniature circuit breaker, 230V, 6kA breaking capacity, 1+N-pole, D-curve, 1A. Active production. RoHS compliant. Sourced to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Miniature Circuit Breakers (MCB)"],"specifications":{"Group Code":"P310","Product Group":"3821","Product class":"B: return restricted, please contact your Siemens partner/contact","Quantity Unit":"1 Piece","Product Family":"Basic Devices","lifecycle_stage":"current","Packaging Quantity":"1","Export Control Regulations":"AL : N / ECCN : N","Packaging dimensions (L x W x H)":"Not available","Compliance with the substance restrictions according to RoHS directive":"Since: 01-06-13","REACH Art. 33 Duty to inform according to the current list of candidates":"Reach Information"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/02752110112366aae79b762489cbbf56.pdf","sourceUrl":"https://sieportal.siemens.com/en-ae/products-services/detail/5SL6501-8CC?tree=CatalogTree","alternativesUrl":"https://aoctrl.com/api/mcp/products/5SL6501-8CC/alternatives.json"},"ai":{"faq":[{"question":"What is the breaking capacity of this MCB?","answer":"The 5SL6501-8CC has a 6 kA breaking capacity at 230 V, which is the maximum fault current it can safely interrupt."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/5SL6501-8CC","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/5SL6501-8CC when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}