{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"5SL6504-7","brand":"Siemens","brandSlug":"siemens","productSlug":"5SL6504-7","canonicalUrl":"https://aoctrl.com/siemens/5SL6504-7","factsUrl":"https://aoctrl.com/api/mcp/products/5SL6504-7","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 5SL6504-7 miniature circuit breaker, 1P+N, C-curve, 4 A, 230 V AC, 6 kA per EN 60898/IEC 60947-2.","salesMarkdown":"The Siemens 5SL6504-7 is a SENTRON miniature circuit breaker (MCB) — a 1P+N, C-curve unit rated 4 A at 230 V AC, with a 6 kA breaking capacity per both EN 60898 and IEC 60947-2. At 36 mm wide (2 modular units), it occupies the same DIN-rail footprint as a standard single-pole plus neutral MCB. The temperature derating table matters: at 40 °C ambient it's good for 3.76 A, at 55 °C only 3.36 A — so if the panel runs hot, factor that into your load. Mechanical life is 10 000 switching cycles typical. ## Panel and integration notes Mounts in any position on standard DIN rail. Sealable terminals are provided — handy for utility-metering or tamper-proof installations. The 1P+N design switches the line and switches the neutral but does not protect it; the neutral is just switched, not monitored for overcurrent. That's typical for single-phase final circuits where the neutral is solidly bonded.","metaTitle":"Siemens 5SL6504-7 SENTRON MCB, 1P+N, C-curve, 4A, 6kA","metaDescription":"Siemens 5SL6504-7 SENTRON miniature circuit breaker, 1P+N, 230 V AC, 6 kA breaking capacity, C-curve, 4 A. Active production. Sourced to order against RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["1-Pole MCB (DIN Rail)"],"specifications":{"Depth":"76 mm","Width":"36 mm","Height":"90 mm","Maximum":"75 °C","Minimum":"-40 °C","Sealable":"Yes","Halogen-Free":"Yes","Silicon-Free":"Yes","Design Of Pole":"1P+N","Number Of Poles":"2","lifecycle_stage":"current","Mounting Position":"any","Installation Depth":"70 mm","Product Brand Name":"SENTRON","Degree Of Pollution":"2","Product Designation":"Miniature circuit breaker","at AC / rated value":"4 A","protection class IP":"IP20, with connected conductors","Overvoltage Category":"III","Energy Limitation Class":"3","according to EN 61346-2":"F","at 30 °C / rated value":"4 A","at 40 °C / rated value":"3.76 A","at 45 °C / rated value":"3.68 A","at 55 °C / rated value":"3.36 A","according to IEC 81346-2":"F","Suitability For Operation":"Residential buildings/infrastructure","Number Of Modular Width Units":"2","Tripping Characteristic Class":"C","at DC / rated value / maximum":"72 V","according to EN 60898 / rated value":"6 kA","supply voltage / at AC / rated value":"230 V","according to IEC 60947-2 / rated value":"6 kA","Type Of Voltage / Of The Operating Voltage":"AC","Value Range / Of The Supply Voltage Frequency":"50/60 Hz","with single-phase operation / at AC / rated value":"250 V","Mechanical Service Life (Switching Cycles) / Typical":"10 000"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":"$9.91","priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/02752110112366aae79b762489cbbf56.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=166755&mlfb=5SL6504-7","alternativesUrl":"https://aoctrl.com/api/mcp/products/5SL6504-7/alternatives.json"},"ai":{"faq":[{"question":"What is the breaking capacity of 5SL6504-7?","answer":"6 kA per both EN 60898 and IEC 60947-2 at 230 V AC. That's the standard rating for most residential and light commercial distribution boards."},{"question":"How do I get pricing and availability for 5SL6504-7?","answer":"Submit an RFQ through this listing. We source and quote it to order; availability and current price are confirmed at quote time."},{"question":"Will 5SL6504-7 drop into a panel specified around 5SL6516-6YA?","answer":"Both are 2-module-wide SENTRON MCBs on the same DIN-rail footprint, so physically they swap. But 5SL6516-6YA is a 16 A B-curve unit — different rating and trip characteristic. Check your load and selectivity requirements before substituting."},{"question":"What compliance documentation is available for 5SL6504-7?","answer":"The part carries CE marking per the Low Voltage Directive and is designed to EN 60898 and IEC 60947-2. It's halogen-free and silicon-free. RoHS and REACH declarations are standard from Siemens for this series."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/5SL6504-7","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/5SL6504-7 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}