{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"5SL6510-6CC","brand":"Siemens","brandSlug":"siemens","productSlug":"5SL6510-6CC","canonicalUrl":"https://aoctrl.com/siemens/5SL6510-6CC","factsUrl":"https://aoctrl.com/api/mcp/products/5SL6510-6CC","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 5SL6510-6CC miniature circuit breaker, B-curve, 10 A, 1P+N, 230 V AC, 6 kA breaking capacity per EN 60898, 2 MW units.","salesMarkdown":"The 6 kA breaking capacity per EN 60898 means it can safely interrupt a fault current up to 6,000 A at 230 V, which covers the majority of domestic and small commercial service entrances. The 1P+N pole configuration switches both the line and neutral, but only the line pole is protected — the neutral pole is switched only, not monitored for overcurrent. This is common in single-phase final subcircuits where the neutral is not fused. The part occupies 2 modular width units (36 mm) on a DIN rail, with a depth of 76 mm and an installation depth of 70 mm — it fits standard 18 mm per-module spacing used in SENTRON and most European distribution boards. The 2 MW width (36 mm) means it takes up two 18 mm slots in a distribution board — check fill factor if you are retrofitting into a densely populated enclosure. Supplementary devices (arc-fault, surge, shunt trip) can be added on the right side via the product extension feature. The closest functional peer in the same SENTRON 5SL family is the 5SL6516-6YA, which is a 16 A B-curve 1P+N MCB with identical dimensions (76 mm depth, 36 mm width, 90 mm height) and the same 6 kA breaking capacity. The only difference that matters for selection is the current rating: 10 A vs 16 A. If your BOM line calls for 10 A protection, the 5SL6510-6CC is the correct part — the 16 A sibling would not trip on a 12 A overload. The mechanical service life, temperature range, and mounting footprint are identical, so a panel designed for one can take the other without rewiring, provided the conductor sizing and load match the higher current.","metaTitle":"Siemens 5SL6510-6CC SENTRON MCB, B-Curve 10 A 1P+N 6 kA","metaDescription":"Siemens SENTRON 5SL6510-6CC miniature circuit breaker, 10 A B-curve, 1P+N, 230 V AC, 6 kA breaking capacity per EN 60898. Active production, sourced to order. IP20 with conductors.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["1-Pole MCB (DIN Rail)"],"specifications":{"Depth":"76 mm","Width":"36 mm","title":"5SL6510-6CC","Height":"90 mm","Maximum":"75 °C","Minimum":"-40 °C","Sealable":"Yes","description":"Miniature circuit breaker 230 V 6kA, 1+N-pole, B, 10 A Circuit breaker 230 V 6kA, 1+N-pole, B, 10 A","Halogen-Free":"Yes","Silicon-Free":"Yes","Design Of Pole":"1P+N","Number Of Poles":"2","lifecycle_stage":"current","Mounting Position":"any","Installation Depth":"70 mm","Product Brand Name":"SENTRON","Degree Of Pollution":"2","Product Designation":"Miniature circuit breaker","protection class IP":"IP20, with connected conductors","Overvoltage Category":"III","Energy Limitation Class":"3","Suitability For Operation":"Residential buildings/infrastructure","at DC rated value maximum":"72 V","Number Of Modular Width Units":"2","Tripping Characteristic Class":"B","supply voltage at AC rated value":"230 V","according to EN 60898 rated value":"6 kA","Type Of Voltage Of The Operating Voltage":"AC","Value Range Of The Supply Voltage Frequency":"50/60 Hz","with single-phase operation at AC rated value":"250 V","vibration resistance according to IEC 60068-2-6":"50 m/s² at 25 to 150 Hz","Product Extension Installable Supplementary Devices":"Yes","power loss [W] for rated value of the current at AC in hot operating state per pole":"1.8 W"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"stockQuantity":0,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/6bd525614f36db90ddc02286de031458.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=533297&mlfb=5SL6510-6CC"},"ai":{"faq":[{"question":"What is the difference between 5SL6510-6CC and 5SL6516-6YA?","answer":"The 5SL6516-6YA is the 16 A B-curve sibling in the same SENTRON 5SL family. Both are 1P+N, 6 kA, same footprint. The only difference is the current rating — 10 A vs 16 A. If your circuit needs 10 A protection, the 5SL6510-6CC is the correct part."},{"question":"Will 5SL6510-6CC drop into a panel designed for 5SL6516-6YA?","answer":"Yes, the two breakers share identical dimensions (76 mm depth, 36 mm width, 90 mm height) and mounting on a 35 mm DIN rail. No rewiring needed — just swap the breaker, provided the load and conductor sizing match the 10 A rating."},{"question":"What compliance documentation does Siemens provide for 5SL6510-6CC?","answer":"The 5SL6510-6CC is designed to EN 60898 (6 kA breaking capacity) and carries an IP20 rating with connected conductors. Siemens typically provides CE, UKCA, and EAC declarations for the SENTRON 5SL series, plus RoHS and REACH compliance statements. Specific certificates should be requested at quote time."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"icboms-matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/5SL6510-6CC","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/5SL6510-6CC when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-08-11T15:51:03.652Z","lastPublished":"2026-08-11T15:51:03.652Z","indexable":true}}