{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"5SL6513-7","brand":"Siemens","brandSlug":"siemens","productSlug":"5SL6513-7","canonicalUrl":"https://aoctrl.com/siemens/5SL6513-7","factsUrl":"https://aoctrl.com/api/mcp/products/5SL6513-7","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 5SL6513-7 miniature circuit breaker, 1P+N, C-curve, 13 A rated, 6 kA breaking capacity per EN 60898, 230 V AC, 2-module width.","salesMarkdown":"It is rated 13 A at 230 V AC, 50/60 Hz, with a C-curve tripping characteristic (5–10× In, typical for motor and lighting loads with moderate inrush). The C-curve means the breaker holds through short-duration inrush up to about 10× rated current — good for small motors, pumps, and fluorescent lighting banks where a B-curve would nuisance-trip. ## Dimensions, mounting, and panel fit Width is 36 mm (2 modular units on a standard DIN rail), depth 76 mm, height 90 mm, with an installation depth of 70 mm. That 36 mm width means it occupies two adjacent 18 mm slots — check your panel layout if you are swapping from a single-pole breaker; you need the extra slot. Mounting position is any, which helps in tight enclosures where the rail is vertical or upside-down. ## Temperature derating — what the ratings actually mean in a warm panel At 40 °C it derates to 12.37 A, at 45 °C to 11.96 A, and at 55 °C to 11.36 A. Power loss per pole is 1.9 W at rated current in hot operating state; for a 2-pole device that is 3.8 W total dissipated inside the enclosure, so factor that into your thermal budget. For BOM planning: this is not a phase-out or last-time-buy part.","metaTitle":"Siemens 5SL6513-7 SENTRON MCB, C-Curve 13A 1P+N 6kA","metaDescription":"Siemens 5SL6513-7 SENTRON miniature circuit breaker, 1P+N, C-curve, 13A rated, 6kA breaking capacity per EN 60898, 230V AC. Active production, sourced to order. Request quote.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["1-Pole MCB (DIN Rail)"],"specifications":{"Depth":"76 mm","Width":"36 mm","title":"5SL6513-7","Height":"90 mm","Maximum":"75 °C","Minimum":"-40 °C","Sealable":"Yes","description":"Miniature circuit breaker 230 V 6kA, 1+N-pole, C, 13A","Halogen-Free":"Yes","Silicon-Free":"Yes","Design Of Pole":"1P+N","Number Of Poles":"2","lifecycle_stage":"current","Mounting Position":"any","at AC rated value":"13 A","Installation Depth":"70 mm","Product Brand Name":"SENTRON","Degree Of Pollution":"2","Product Designation":"Miniature circuit breaker","protection class IP":"IP20, with connected conductors","Overvoltage Category":"III","at 30 °C rated value":"13 A","at 40 °C rated value":"12.37 A","at 45 °C rated value":"11.96 A","at 55 °C rated value":"11.36 A","Energy Limitation Class":"3","Suitability For Operation":"Residential buildings/infrastructure","at DC rated value maximum":"72 V","Number Of Modular Width Units":"2","Tripping Characteristic Class":"C","supply voltage at AC rated value":"230 V","according to EN 60898 rated value":"6 kA","according to IEC 60947-2 rated value":"6 kA","Type Of Voltage Of The Operating Voltage":"AC","Value Range Of The Supply Voltage Frequency":"50/60 Hz","with single-phase operation at AC rated value":"250 V","Mechanical Service Life (Operating Cycles) Typical":"10 000","Product Extension Installable Supplementary Devices":"Yes","power loss [W] for rated value of the current at AC in hot operating state per pole":"1.9 W"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":"$7.05","stockQuantity":0,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/6bd525614f36db90ddc02286de031458.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=257913&mlfb=5SL6513-7"},"ai":{"faq":[{"question":"What is the breaking capacity of 5SL6513-7?","answer":"The breaking capacity is 6 kA per both EN 60898 and IEC 60947-2 at 230 V AC. That is the maximum fault current the breaker can safely interrupt."},{"question":"Will 5SL6513-7 drop into a panel specified for 5SL4363-7?","answer":"Both are 1P+N, 2-module-width (36 mm) SENTRON MCBs on the same DIN-rail footprint, so the mechanical fit is identical. The difference is the current rating and possibly the curve — 5SL4363-7 is a different rating; verify your load current and tripping curve before swapping."},{"question":"Where can I buy 5SL6513-7?","answer":"This part is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time — submit a request for quote for the latest position."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"icboms-matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/5SL6513-7","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/5SL6513-7 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-08-11T15:51:03.652Z","lastPublished":"2026-08-11T15:51:03.652Z","indexable":true}}