{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"5SL6610-7","brand":"Siemens","brandSlug":"siemens","productSlug":"5SL6610-7","canonicalUrl":"https://aoctrl.com/siemens/5SL6610-7","factsUrl":"https://aoctrl.com/api/mcp/products/5SL6610-7","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 5SL6610-7 miniature circuit breaker, 3P+N, 10 A, C characteristic, 6 kA breaking capacity at 400 V AC, 4 modular width units.","salesMarkdown":"## What the ratings mean for fit The Siemens SENTRON 5SL6610-7 is a 3P+N miniature circuit breaker rated 10 A at 400 V AC with a C tripping characteristic. The C-curve (magnetic trip between 5× and 10× In) is the standard choice for general-purpose branch circuits feeding mixed resistive and light inductive loads — think lighting, socket outlets, small motor starters in residential or light commercial panels. The 6 kA breaking capacity per EN 60898 and IEC 60947-2 means it safely clears a fault up to that prospective short-circuit current without welding contacts or rupturing the case; for most domestic and infrastructure distribution boards fed by a transformer of similar kVA rating, that's sufficient headroom. Thermal derating is published: the breaker carries its full 10 A at 30 °C ambient, drops to 9.52 A at 40 °C, 9 A at 45 °C, and 8.74 A at 55 °C. If the panel ambient runs above 30 °C — common in a sealed outdoor enclosure or a crowded DIN-rail cabinet — size the upstream load to the derated value, not the nameplate 10 A. Four modular width units (72 mm wide) snap onto a standard DIN rail; the 76 mm depth leaves clearance behind a 100 mm deep enclosure. Installation depth is 70 mm, so the breaker body sits flush with the rail. IP20 with connected conductors — fine for a dry indoor panel, not for washdown zones. ## Integration notes for the panel builder Mounting position is any — no derating for horizontal or inverted orientation. The breaker is sealable (padlockable toggle) for lockout/tagout compliance. Halogen-free and silicon-free construction matters for environments sensitive to outgassing, such as clean rooms or sealed enclosures near optical equipment. Overvoltage category III and pollution degree 2 — standard for fixed-installation distribution boards. Energy limitation class 3 means it limits let-through energy to a level that downstream components (cables, contactors) can survive a fault without additional coordination.","metaTitle":"Siemens 5SL6610-7 SENTRON MCB, 3P+N, 10 A, C-Curve, 6 kA","metaDescription":"Siemens 5SL6610-7 SENTRON miniature circuit breaker, 3P+N, 10 A, C characteristic, 6 kA breaking capacity per EN 60898 / IEC 60947-2. 400 V AC, 4 MWU, IP20. Current production — so","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["4-Pole MCB (DIN Rail)"],"specifications":{"Depth":"76 mm","Width":"72 mm","title":"5SL6610-7","Height":"90 mm","Maximum":"75 °C","Minimum":"-40 °C","Sealable":"Yes","description":"Miniature circuit breaker 400 V 6kA, 3+N-pole, C, 10 A","Halogen-Free":"Yes","Silicon-Free":"Yes","Design Of Pole":"3P+N","Number Of Poles":"4","lifecycle_stage":"current","Mounting Position":"any","Installation Depth":"70 mm","Product Brand Name":"SENTRON","Degree Of Pollution":"2","Product Designation":"Miniature circuit breaker","at AC / rated value":"10 A","protection class IP":"IP20, with connected conductors","Overvoltage Category":"III","Energy Limitation Class":"3","according to EN 61346-2":"F","at 30 °C / rated value":"10 A","at 40 °C / rated value":"9.52 A","at 45 °C / rated value":"9 A","at 55 °C / rated value":"8.74 A","according to IEC 81346-2":"F","Suitability For Operation":"Residential buildings/infrastructure","Number Of Modular Width Units":"4","Tripping Characteristic Class":"C","at DC / rated value / maximum":"72 V","according to EN 60898 / rated value":"6 kA","supply voltage / at AC / rated value":"400 V","according to IEC 60947-2 / rated value":"6 kA","Type Of Voltage / Of The Operating Voltage":"AC","with multi-phase operation / at AC / maximum":"440 V","Value Range / Of The Supply Voltage Frequency":"50/60 Hz","with multi-phase operation / at AC / rated value":"440 V","Mechanical Service Life (Switching Cycles) / Typical":"10 000"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"stockQuantity":0,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/a6937528a5840a79b6fa126710d0843d.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=27376&mlfb=5SL6610-7"},"ai":{"faq":[{"question":"What is the breaking capacity of the 5SL6610-7?","answer":"6 kA per EN 60898 and IEC 60947-2 at 400 V AC. That's the standard breaking capacity for residential and light commercial distribution boards."},{"question":"What is the 5SL6610-7 used for?","answer":"It's a 3P+N miniature circuit breaker for AC branch circuits rated 10 A, C-curve, suited for residential buildings and infrastructure — lighting, socket outlets, small motor loads."},{"question":"Where can I buy the 5SL6610-7?","answer":"Sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"icboms-matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/5SL6610-7","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/5SL6610-7 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-08-11T15:51:03.652Z","lastPublished":"2026-08-11T15:51:03.652Z","indexable":true}}