{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"5SL6613-7","brand":"Siemens","brandSlug":"siemens","productSlug":"5SL6613-7","canonicalUrl":"https://aoctrl.com/siemens/5SL6613-7","factsUrl":"https://aoctrl.com/api/mcp/products/5SL6613-7","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON miniature circuit breaker, 5SL6613-7, 3P+N, C-curve, 13 A, 400 V AC, 6 kA breaking capacity per EN 60898, 4 MW width.","salesMarkdown":"## What this breaker is and what it protects It is rated for 400 V AC at 50/60 Hz, with a breaking capacity of 6 kA per both EN 60898 and IEC 60947-2 — that figure governs its ability to safely interrupt a fault up to 6 kA without welding contacts or cascading failure upstream. ## Panel fit and mechanical constraints This 4-pole breaker occupies 4 modular width units (72 mm) on a DIN rail, with a depth of 76 mm and a height of 90 mm. That means an existing panel layout using other 5SL breakers can take this unit without reworking the accessory rail. ## Electrical ratings and coordination notes Maximum operating voltage is 440 V AC for multi-phase operation; the breaker also carries a DC rating of 72 V maximum, so it can be used on a 48 V or 60 V DC bus, but not on a 110 V DC circuit. That is low enough to ignore for thermal derating in a standard 12-module enclosure, but worth checking if the breaker is packed tight in a high-ambient panel.","metaTitle":"Siemens 5SL6613-7 SENTRON MCB, 3P+N, C-Curve, 13A, 6kA","metaDescription":"Siemens 5SL6613-7 SENTRON miniature circuit breaker, 400V AC, 6kA breaking capacity per EN 60898, 3P+N, C-curve, 13A. Active production. Quoted to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["4-Pole MCB (DIN Rail)"],"specifications":{"Depth":"76 mm","Width":"72 mm","title":"5SL6613-7","Height":"90 mm","Maximum":"75 °C","Minimum":"-40 °C","Sealable":"Yes","description":"Miniature circuit breaker 400 V 6kA, 3+N-pole, C, 13A","Halogen-Free":"Yes","Silicon-Free":"Yes","Design Of Pole":"3P+N","Number Of Poles":"4","lifecycle_stage":"current","Mounting Position":"any","Installation Depth":"70 mm","Product Brand Name":"SENTRON","Degree Of Pollution":"2","Product Designation":"Miniature circuit breaker","protection class IP":"IP20, with connected conductors","Overvoltage Category":"III","Energy Limitation Class":"3","Suitability For Operation":"Residential buildings/infrastructure","at DC rated value maximum":"72 V","Number Of Modular Width Units":"4","Tripping Characteristic Class":"C","supply voltage at AC rated value":"400 V","according to EN 60898 rated value":"6 kA","according to IEC 60947-2 rated value":"6 kA","Type Of Voltage Of The Operating Voltage":"AC","with multi-phase operation at AC maximum":"440 V","Value Range Of The Supply Voltage Frequency":"50/60 Hz","with multi-phase operation at AC rated value":"440 V","Mechanical Service Life (Operating Cycles) Typical":"10 000","Product Extension Installable Supplementary Devices":"Yes","power loss [W] for rated value of the current at AC in hot operating state per pole":"1.5 W"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"stockQuantity":0,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/a6937528a5840a79b6fa126710d0843d.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=529266&mlfb=5SL6613-7"},"ai":{"faq":[{"question":"Where can I buy the 5SL6613-7 and get a price?","answer":"The 5SL6613-7 is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time."},{"question":"What is the closest functional alternative — the 5SL4363-7?","answer":"The 5SL4363-7 is a 3-pole (3P) version at 10 kA breaking capacity, while the 5SL6613-7 is 3P+N at 6 kA. The 5SL4363-7 is 54 mm wide (3 MW) versus 72 mm (4 MW) for the 5SL6613-7, so it will not drop into the same DIN-rail space without a blanking module or a different enclosure cutout."},{"question":"What is the depth of the 5SL6613-7?","answer":"The depth is 76 mm, with an installation depth of 70 mm."},{"question":"What is the width of the 5SL6613-7?","answer":"The width is 72 mm, which corresponds to 4 modular width units on a DIN rail."},{"question":"What compliance documentation does Siemens provide for the 5SL6613-7?","answer":"The breaker is rated per EN 60898 and IEC 60947-2 for breaking capacity, carries IP20 protection, and is halogen-free and silicon-free. It is designed for residential and infrastructure installations per the SENTRON product line."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"icboms-matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/5SL6613-7","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/5SL6613-7 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-08-11T15:51:03.652Z","lastPublished":"2026-08-11T15:51:03.652Z","indexable":true}}