{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"5SL7106-7RC","brand":"Siemens","brandSlug":"siemens","productSlug":"5SL7106-7RC","canonicalUrl":"https://aoctrl.com/siemens/5SL7106-7RC","factsUrl":"https://aoctrl.com/api/mcp/products/5SL7106-7RC","rawCanonicalId":null},"summary":{"shortDescription":"Siemens Betagard miniature circuit breaker, 5SL7106-7RC, 1-pole, C-curve, 6 A, 15 kA per EN 60898, 20 kA per IEC 60947-2, 240/415 V AC, 1 MW unit.","salesMarkdown":"It breaks fault currents up to 15 kA per EN 60898 and 20 kA per IEC 60947-2 at 240 V AC, making it suitable for industrial panel protection where the prospective short-circuit current sits between those two standards' test conditions. The 15 kA breaking capacity under EN 60898 is the value used for residential and light commercial coordination; the 20 kA figure under IEC 60947-2 is the industrial rating, tested with a different power-factor and making-capacity sequence. If your panel SCCR study calls for 18 kA at the loadcenter, the 60947-2 rating covers it; if the spec references EN 60898 only, the 15 kA limit governs. The 1-pole design occupies one modular width unit (18 mm) on the DIN rail, with a depth of 76 mm and an installation depth of 70 mm — standard for a 1 MW device, so it fits existing Betagard or SENTRON distribution boards without re-spacing. In a multi-pole assembly, sum the per-pole losses for thermal derating inside a crowded enclosure. ## Integration notes The 18 mm width (1 MW) matches the Betagard and SENTRON modular grid; downstream neutral bars and busbar systems designed for 1-pole spacing accept it without adapters. Sealable per the spec, so the installer can lock the toggle position after commissioning to prevent unauthorized switching.","metaTitle":"Siemens 5SL7106-7RC Betagard MCB, 1P C-curve 6A 15kA","metaDescription":"Siemens Betagard 5SL7106-7RC miniature circuit breaker, 1-pole C-curve 6A, 15kA per EN 60898, 20kA per IEC 60947-2. Active production. Quoted to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["1-Pole MCB (DIN Rail)"],"specifications":{"Depth":"76 mm","Width":"18 mm","title":"5SL7106-7RC","Height":"90 mm","Maximum":"75 °C","Minimum":"-40 °C","Sealable":"Yes","description":"Miniature circuit breaker 240/415 V 1-pole 15 kA C 6","Halogen-Free":"Yes","Silicon-Free":"Yes","Design Of Pole":"1P","Number Of Poles":"1","lifecycle_stage":"current","Mounting Position":"any","Installation Depth":"70 mm","Product Brand Name":"Betagard","Degree Of Pollution":"2","Product Designation":"Miniature circuit breaker","protection class IP":"IP20, with connected conductors","Overvoltage Category":"III","Suitability For Operation":"Industry","Number Of Modular Width Units":"1","Tripping Characteristic Class":"C","supply voltage at AC rated value":"240 V","according to EN 60898 rated value":"15 kA","according to IEC 60947-2 rated value":"20 kA","Type Of Voltage Of The Operating Voltage":"AC","with multi-phase operation at AC maximum":"440 V","Value Range Of The Supply Voltage Frequency":"50/60 Hz","with multi-phase operation at AC rated value":"440 V","with single-phase operation at AC rated value":"440 V","vibration resistance according to IEC 60068-2-6":"yes","Mechanical Service Life (Operating Cycles) Typical":"10 000","power loss [W] for rated value of the current at AC in hot operating state per pole":"1.6 W"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"stockQuantity":0,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/fa6bd2f18c9726416ab7419aac12ad0e.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=646567&mlfb=5SL7106-7RC"},"ai":{"faq":[{"question":"How do I get current pricing and availability for 5SL7106-7RC?","answer":"This part is sourced to order through independent distribution. Submit an RFQ for a firm quote with current pricing and confirmed availability."},{"question":"Will 5SL7106-7RC drop into a panel specified around 5SL6006-7 without rewiring?","answer":"Yes, both are 1-pole C-curve MCBs in an 18 mm footprint with the same depth and DIN-rail mounting. The 5SL7106-7RC carries a higher breaking capacity (15 kA vs 6 kA per EN 60898), so it is a direct mechanical replacement but offers greater fault-current headroom. Verify the neutral switching requirement — the 5SL6006-7 is a 1P+N device with switched neutral, while the 5SL7106-7RC is 1-pole only."},{"question":"What compliance documentation does Siemens provide for 5SL7106-7RC?","answer":"The part carries a CE marking per the Low Voltage Directive and is designed to EN 60898 and IEC 60947-2. It is halogen-free and silicon-free. Specific RoHS and REACH declarations are available from the manufacturer upon request."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"icboms-matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/5SL7106-7RC","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/5SL7106-7RC when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-08-11T15:51:03.652Z","lastPublished":"2026-08-11T15:51:03.652Z","indexable":true}}