{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"5SL7206-3RC","brand":"Siemens","brandSlug":"siemens","productSlug":"5SL7206-3RC","canonicalUrl":"https://aoctrl.com/siemens/5SL7206-3RC","factsUrl":"https://aoctrl.com/api/mcp/products/5SL7206-3RC","rawCanonicalId":null},"summary":{"shortDescription":"Siemens Betagard miniature circuit breaker, 2-pole, K characteristic, 6 A rated, 15 kA breaking capacity at 415 V AC, order code 5SL7206-3RC.","salesMarkdown":"The Siemens Betagard 5SL7206-3RC is a 2-pole miniature circuit breaker (MCB) with a K tripping characteristic, rated 6 A at 415 V AC and a breaking capacity of 15 kA per EN 60898. The IP20 rating applies with connected conductors; the housing is sealable and halogen-free, suitable for clean-room or low-smoke environments. ## Thermal derating & ratings Rated 6 A at 50 °C ambient; derate to 5.7 A at 60 °C. At 30 °C the breaker handles 6.5 A continuous. The K characteristic means magnetic trip at 8–12× In, so it holds through motor inrush but clears fast on hard shorts. Overvoltage category III, pollution degree 2 — standard for distribution panels.","metaTitle":"Siemens Betagard 5SL7206-3RC MCB, 2P K-curve 6A 15kA","metaDescription":"Siemens Betagard 5SL7206-3RC miniature circuit breaker, 2-pole, K characteristic, 6 A, 15 kA breaking capacity. Active production. Sourced to order against RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["2-Pole MCB (DIN Rail)"],"specifications":{"Depth":"76 mm","Width":"36 mm","title":"5SL7206-3RC","Height":"90 mm","Maximum":"75 °C","Minimum":"-40 °C","Sealable":"Yes","description":"Miniature Circuit Breaker 6A 2-pole K characteristic 15kA","Halogen-Free":"Yes","Silicon-Free":"Yes","Design Of Pole":"2P","Number Of Poles":"2","lifecycle_stage":"current","Mounting Position":"any","Installation Depth":"70 mm","Product Brand Name":"Betagard","Degree Of Pollution":"2","Product Designation":"Miniature circuit breaker","acc. to IEC 81346-2":"F","at AC / rated value":"6 A","protection class IP":"IP20, with connected conductors","Overvoltage Category":"III","acc. to DIN EN 61346-2":"F","at 30 °C / rated value":"6.5 A","at 40 °C / rated value":"6.3 A","at 45 °C / rated value":"6.1 A","at 50 °C / rated value":"6 A","at 55 °C / rated value":"5.9 A","at 60 °C / rated value":"5.7 A","Number Of Modular Width Units":"2","Tripping Characteristic Class":"K","at DC / rated value / maximum":"72 V","acc. to EN 60898 / rated value":"15 kA","Product Feature / Touch Protection":"Yes","supply voltage / at AC / rated value":"415 V","Type Of Voltage / Of The Operating Voltage":"AC","vibration resistance / acc. to IEC 60068-2-6":"50 m/s² at 25 to 150 Hz","with multi-phase operation / at AC / maximum":"440 V","Product Component / Neutral Conductor Switching":"No","with multi-phase operation / at AC / rated value":"440 V","with single-phase operation / at AC / rated value":"440 V"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"stockQuantity":0,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/c683bc27b90811572a4bddff766a9808.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=1502409&mlfb=5SL7206-3RC"},"ai":{"faq":[{"question":"Where can I buy 5SL7206-3RC and get a price?","answer":"The 5SL7206-3RC is sourced to order against an RFQ through independent distribution. Submit an RFQ for current availability and pricing — confirmed at quote time."},{"question":"What is the breaking capacity of 5SL7206-3RC?","answer":"15 kA per EN 60898 at 415 V AC. That is the standard interrupting rating for this class — sufficient for most secondary distribution panels."},{"question":"Will 5SL7206-3RC drop into a panel built for 5SL6016-7KL?","answer":"Both are 2-pole MCBs on a 36 mm DIN footprint, so the physical fit is the same. The 5SL7206-3RC uses a K characteristic vs the B curve of the 5SL6016-7KL — check that the load's inrush profile matches K curve (motor/transformer duty) and that the 6 A rating and 15 kA breaking capacity meet your circuit requirements."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"icboms-matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/5SL7206-3RC","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/5SL7206-3RC when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-08-11T15:51:03.652Z","lastPublished":"2026-08-11T15:51:03.652Z","indexable":true}}