{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"5SL7225-7RC","brand":"Siemens","brandSlug":"siemens","productSlug":"5SL7225-7RC","canonicalUrl":"https://aoctrl.com/siemens/5SL7225-7RC","factsUrl":"https://aoctrl.com/api/mcp/products/5SL7225-7RC","rawCanonicalId":null},"summary":{"shortDescription":"Siemens Betagard miniature circuit breaker, 5SL7225-7RC, 2-pole (2P), 25 A rated, C tripping characteristic, 15 kA breaking capacity per EN 60898, 20 kA per IEC 60947-2, 415 V AC, 2 modular width units (18 mm).","salesMarkdown":"The Siemens Betagard 5SL7225-7RC is a 2-pole miniature circuit breaker rated 25 A with a C tripping characteristic, designed for AC circuits up to 415 V (440 V max multi-phase). ## Breaking capacity — what those numbers mean for your panel The EN 60898 number is the one for residential/commercial distribution boards; the IEC 60947-2 rating is the industrial one, and it's higher — 20 kA at 415 V. For a 25 A feeder in an industrial panel with a transformer behind it, that's solid headroom. The 15 kA figure is the standard for most building-level sub-distribution. ## Mounting and environment — panel-fit details IP20 with conductors connected, so it's for inside a panel, not out in washdown. Sealable, halogen-free, silicon-free. Ambient temperature range -40 °C to 75 °C, but the current derating curve matters: at 40 °C it's 23.75 A, at 50 °C it's 22.5 A, at 60 °C it's 21.5 A.","metaTitle":"Siemens Betagard 5SL7225-7RC Miniature Circuit Breaker, 2P C","metaDescription":"Siemens Betagard 5SL7225-7RC miniature circuit breaker, 2-pole, 25 A, C-curve, 15 kA per EN 60898. Active production. Quoted to order against RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["2-Pole MCB (DIN Rail)"],"specifications":{"Depth":"76 mm","Width":"18 mm","title":"5SL7225-7RC","Height":"90 mm","Maximum":"75 °C","Minimum":"-40 °C","Sealable":"Yes","description":"Miniature circuit breaker 415 V 2-pole 15 kA C 25","Halogen-Free":"Yes","Silicon-Free":"Yes","Number Of Poles":"2","Type Of Voltage":"AC","lifecycle_stage":"current","Mounting Position":"any","Installation Depth":"70 mm","Product Brand Name":"Betagard","Degree Of Pollution":"2","Product Designation":"Miniature circuit breaker","at AC / rated value":"25 A","protection class IP":"IP20, with connected conductors","Overvoltage Category":"III","Number Of Poles / Note":"2P","at 30 °C / rated value":"25 A","at 40 °C / rated value":"23.75 A","at 45 °C / rated value":"23.25 A","at 50 °C / rated value":"22.5 A","at 55 °C / rated value":"22 A","at 60 °C / rated value":"21.5 A","Suitability For Operation":"Industry","Number Of Modular Width Units":"2","Tripping Characteristic Class":"C","acc. to EN 60898 / rated value":"15 kA","acc. to IEC 60947-2 / rated value":"20 kA","Product Feature / Touch Protection":"Yes","supply voltage / at AC / rated value":"415 V","Supply Voltage Frequency / Rated Value":"50/60 Hz","with multi-phase operation / at AC / maximum":"440 V","Product Function / Neutral Conductor Switching":"No","with multi-phase operation / at AC / rated value":"440 V","with single-phase operation / at AC / rated value":"440 V","Mechanical Service Life (Operating Cycles) / Typical":"10 000"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"stockQuantity":0,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/6e3b7ad132eb81a4d786bcae8a37a4a2.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=646356&mlfb=5SL7225-7RC"},"ai":{"faq":[],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"icboms-matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/5SL7225-7RC","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/5SL7225-7RC when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-08-11T15:51:03.652Z","lastPublished":"2026-08-11T15:51:03.652Z","indexable":true}}