{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"5SL7232-8RC","brand":"Siemens","brandSlug":"siemens","productSlug":"5SL7232-8RC","canonicalUrl":"https://aoctrl.com/siemens/5SL7232-8RC","factsUrl":"https://aoctrl.com/api/mcp/products/5SL7232-8RC","rawCanonicalId":null},"summary":{"shortDescription":"Siemens Betagard miniature circuit breaker, 5SL7232-8RC, 2-pole, D tripping characteristic, 32 A rated current, 15 kA breaking capacity per IEC 60947-2, 415 V AC.","salesMarkdown":"The Siemens Betagard 5SL7232-8RC is a 2-pole miniature circuit breaker with a D tripping characteristic, rated 32 A at 415 V AC and a breaking capacity of 15 kA per both EN 60898 and IEC 60947-2. The D-curve tolerates high inrush currents before tripping magnetically, suiting loads like small motors or transformers. Rated for 415 V AC phase-to-phase or phase-to-neutral, with a maximum operating voltage of 440 V AC in single- or multi-phase operation. Breaking capacity of 15 kA at 415 V per IEC 60947-2 means this breaker can safely interrupt a fault current up to 15,000 A without welding contacts or cascading failure upstream — enough for most industrial sub-distribution boards fed by a transformer in the 630 kVA range. Temperature derating is published: at 40 °C ambient it carries 30.4 A, at 50 °C it's 28.8 A, at 60 °C it's 27.52 A. Width is 18 mm (2 modular units), depth 76 mm, height 90 mm, installation depth 70 mm. Touch protection is integrated, meaning live busbar and terminals are shielded to IP2X even with the breaker snapped in place.","metaTitle":"Siemens Betagard 5SL7232-8RC MCB, 2P D 32 A 15 kA","metaDescription":"Siemens Betagard 5SL7232-8RC miniature circuit breaker, 2-pole, D-curve, 32 A, 15 kA per IEC 60947-2, 415 V AC. Current production. Sourced to order against RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["2-Pole MCB (DIN Rail)"],"specifications":{"Depth":"76 mm","Width":"18 mm","title":"5SL7232-8RC","Height":"90 mm","Maximum":"75 °C","Minimum":"-40 °C","Sealable":"Yes","description":"Miniature circuit breaker 415 V 2-pole 15 kA D 32","Halogen-Free":"Yes","Silicon-Free":"Yes","Design Of Pole":"2P","Number Of Poles":"2","lifecycle_stage":"current","Mounting Position":"any","Installation Depth":"70 mm","Product Brand Name":"Betagard","Degree Of Pollution":"2","Product Designation":"Miniature circuit breaker","at AC / rated value":"32 A","protection class IP":"IP20, with connected conductors","Overvoltage Category":"III","at 30 °C / rated value":"32 A","at 40 °C / rated value":"30.4 A","at 45 °C / rated value":"29.76 A","at 50 °C / rated value":"28.8 A","at 55 °C / rated value":"28.16 A","at 60 °C / rated value":"27.52 A","Suitability For Operation":"Industry","Number Of Modular Width Units":"2","Tripping Characteristic Class":"D","Product Feature / Touch Protection":"Yes","according to EN 60898 / rated value":"15 kA","supply voltage / at AC / rated value":"415 V","according to IEC 60947-2 / rated value":"15 kA","Type Of Voltage / Of The Operating Voltage":"AC","with multi-phase operation / at AC / maximum":"440 V","Value Range / Of The Supply Voltage Frequency":"50/60 Hz","Product Component / Neutral Conductor Switching":"No","with multi-phase operation / at AC / rated value":"440 V","with single-phase operation / at AC / rated value":"440 V","Mechanical Service Life (Switching Cycles) / Typical":"10 000"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"stockQuantity":0,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/28ac1747522c447d8b78c853f5e6c9d2.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=646359&mlfb=5SL7232-8RC"},"ai":{"faq":[{"question":"Does the 5SL7232-8RC drop into a panel specified around the 5SL6016-7KL?","answer":"Both are 2-module-width (18 mm) DIN-rail breakers, so the physical footprint is the same. The 5SL7232-8RC is a D-curve 32 A 15 kA unit; the 5SL6016-7KL is a different characteristic and rating — verify the circuit's overload and short-circuit requirements before swapping."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"icboms-matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/5SL7232-8RC","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/5SL7232-8RC when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-08-11T15:51:03.652Z","lastPublished":"2026-08-11T15:51:03.652Z","indexable":true}}