{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"5SL7410-7RC","brand":"Siemens","brandSlug":"siemens","productSlug":"5SL7410-7RC","canonicalUrl":"https://aoctrl.com/siemens/5SL7410-7RC","factsUrl":"https://aoctrl.com/api/mcp/products/5SL7410-7RC","rawCanonicalId":null},"summary":{"shortDescription":"Siemens Betagard miniature circuit breaker, 5SL7410-7RC, 4-pole, C-curve, 10 A, 415 V AC, 15 kA (EN 60898) / 20 kA (IEC 60947-2), 4 modular width units.","salesMarkdown":"## What this 4-pole C-curve MCB is for Four modular width units (18 mm each) mean it occupies 72 mm of rail — standard for a 4-pole MCB in this class. The IP20 enclosure with connected conductors is typical for enclosed panel mounting; not for wet or outdoor locations without a secondary enclosure. Two breaking-capacity ratings let you match the standard that governs your panel design. Under EN 60898 (household / similar installations) it is rated 15 kA; under IEC 60947-2 (industrial switchgear) it is rated 20 kA. At 20 kA it clears faults without cascading to upstream devices, preserving selectivity in a multi-level distribution scheme. Power loss is 1.1 W per pole in hot operating state — low enough that thermal buildup in a densely populated enclosure is manageable. Snap-on DIN rail mounting, any position.","metaTitle":"Siemens Betagard 5SL7410-7RC MCB, 4P C 10 A 15 kA EN 60898","metaDescription":"Siemens Betagard 5SL7410-7RC miniature circuit breaker, 4-pole C-curve 10 A, 15 kA (EN 60898) / 20 kA (IEC 60947-2), 415 V AC. Current production. Sourced to order against RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["4-Pole MCB (DIN Rail)"],"specifications":{"Depth":"76 mm","Width":"18 mm","title":"5SL7410-7RC","Height":"90 mm","Maximum":"75 °C","Minimum":"-40 °C","Sealable":"Yes","description":"Miniature circuit breaker 415 V 4-pole 15 kA C 10","Halogen-Free":"Yes","Silicon-Free":"Yes","Design Of Pole":"4P","Number Of Poles":"4","lifecycle_stage":"current","Mounting Position":"any","Installation Depth":"70 mm","Product Brand Name":"Betagard","Degree Of Pollution":"2","Product Designation":"Miniature circuit breaker","protection class IP":"IP20, with connected conductors","Overvoltage Category":"III","Suitability For Operation":"Industry","Number Of Modular Width Units":"4","Tripping Characteristic Class":"C","supply voltage at AC rated value":"415 V","according to EN 60898 rated value":"15 kA","according to IEC 60947-2 rated value":"20 kA","Type Of Voltage Of The Operating Voltage":"AC","with multi-phase operation at AC maximum":"440 V","Value Range Of The Supply Voltage Frequency":"50/60 Hz","with multi-phase operation at AC rated value":"440 V","with single-phase operation at AC rated value":"440 V","vibration resistance according to IEC 60068-2-6":"yes","Mechanical Service Life (Operating Cycles) Typical":"10 000","power loss [W] for rated value of the current at AC in hot operating state per pole":"1.1 W"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"stockQuantity":0,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/02757ade4d1e57f8da8815da27fb5ae8.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=646404&mlfb=5SL7410-7RC"},"ai":{"faq":[{"question":"What are the key ratings of the 5SL7410-7RC?","answer":"4-pole C-curve MCB rated 10 A at 415 V AC, with breaking capacity 15 kA per EN 60898 and 20 kA per IEC 60947-2. It occupies 4 modular width units (72 mm) on a DIN rail."},{"question":"Where can I buy the 5SL7410-7RC?","answer":"This part is sourced to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time."},{"question":"What is the difference between the 5SL7410-7RC and the 5SL4363-7?","answer":"The 5SL4363-7 is a 3-pole SENTRON MCB rated 10 kA (both EN 60898 and IEC 60947-2) at 400 V AC, versus the Betagard 5SL7410-7RC which is 4-pole with higher breaking capacity (15/20 kA) at 415 V. The 5SL4363-7 is also labeled for residential/infrastructure use, while the 5SL7410-7RC is rated for industry. They are not direct drop-in replacements due to pole count and footprint differences."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"icboms-matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/5SL7410-7RC","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/5SL7410-7RC when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-08-11T15:51:03.652Z","lastPublished":"2026-08-11T15:51:03.652Z","indexable":true}}