{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"5SM2325-6","brand":"Siemens","brandSlug":"siemens","productSlug":"5SM2325-6","canonicalUrl":"https://aoctrl.com/siemens/5SM2325-6","factsUrl":"https://aoctrl.com/api/mcp/products/5SM2325-6","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 5SM2325-6 RCD unit, 2-pole, type A, In 63 A, 30 mA, Un AC 230 V.","salesMarkdown":"It is a type A, instantaneous (no time delay) RCD rated 63 A with a 30 mA trip threshold, for 230 V AC single-phase circuits at 50 Hz only. The 71 mm width (2 modular width units) and 70 mm depth match the standard DIN-rail footprint, so it clips directly alongside a 5SY breaker in a residential or light-commercial distribution board. The instantaneous design (no time delay) means it trips within the standard RCD response window; do not use it downstream of a time-delayed RCD if you need selectivity — for that you would need an S-type (time-delayed) RCD instead. Rated insulation voltage is 460 V with a 4 kV surge withstand (overvoltage category III), so the device is suitable for the incoming side of a distribution board, not just sub-circuits. IP20 protection applies only when the distribution board is installed and conductors are connected — this is a panel-internal device, not rated for wet or outdoor locations.","metaTitle":"Siemens 5SM2325-6 SENTRON RCD, 2-pole, 63 A, 30 mA, 230 V AC","metaDescription":"Siemens SENTRON 5SM2325-6 RCD unit for 5SY, 2-pole type A, 63 A rated, 30 mA sensitivity, 230 V AC. Active production. Available to order — request quote.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Residual Current Breakers (RCCB/RCBO)"],"specifications":{"Depth":"70 mm","Width":"71 mm","title":"5SM2325-6","Height":"90 mm","Maximum":"45 °C","Minimum":"-25 °C","Sealable":"No","description":"RC unit for 5SY, 2-pole, type A, In: 63 A, 30 mA, Un AC: 230 V","Number Of Poles":"2","lifecycle_stage":"current","Fastening Method":"REG","Mounting Position":"any","Installation Depth":"70 mm","Product Brand Name":"SENTRON","Degree Of Pollution":"2","Maximum Permissible":"75 °C","Minimum Permissible":"-40 °C","Product Designation":"RCD-unit","protection class IP":"IP20, if the distribution board is installed, with connected conductors","Overvoltage Category":"III","Design Of The Product":"instantaneous","OFF-delay time adjustable":"No","Number Of Modular Width Units":"2","Rated Fault Current Adjustable":"No","Protection Function False Tripping":"Yes","insulation voltage (Ui) rated value":"460 V","Surge Voltage Resistance Rated Value":"4 000 V","Value Range Of The Operating Frequency":"50 Hz","reference code according to IEC 81346-2":"F","Value Range Of The Supply Voltage Frequency":"50 Hz","Supply Voltage For Testing Equipment Minimum":"195 V","Mechanical Service Life (Operating Cycles) Typical":"10 000","for rated value of the current at AC in hot operating state per pole":"4.6 W"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"stockQuantity":0,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/3edc6616f3dc0678f3e02b133cd336b9.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=278617&mlfb=5SM2325-6"},"ai":{"faq":[{"question":"Where can I buy 5SM2325-6 and get a price?","answer":"The 5SM2325-6 is sourced to order against an RFQ through independent distribution channels. Submit a request for quote to confirm current availability and pricing — no stock count or price figure is published here."},{"question":"Will 5SM2325-6 drop into a panel specified for 5SL4363-7 without rewiring?","answer":"No, the 5SL4363-7 is a 3-pole miniature circuit breaker (MCB) with a 54 mm width, while the 5SM2325-6 is a 2-pole RCD at 71 mm width. The footprint, function, and wiring differ — they are not drop-in replacements for each other."},{"question":"What is the 5SM2325-6's depth?","answer":"The 5SM2325-6 has a depth of 70 mm (installation depth also 70 mm), with a width of 71 mm and height of 90 mm."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"icboms-matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/5SM2325-6","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/5SM2325-6 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-08-11T15:51:03.652Z","lastPublished":"2026-08-11T15:51:03.652Z","indexable":true}}