{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"5SM2327-6","brand":"Siemens","brandSlug":"siemens","productSlug":"5SM2327-6","canonicalUrl":"https://aoctrl.com/siemens/5SM2327-6","factsUrl":"https://aoctrl.com/api/mcp/products/5SM2327-6","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 5SM2327-6, 2-pole instantaneous RCD, 100 A at AC, 30 mA Type A, 4 MW, IP20.","salesMarkdown":"The 5SM2327-6: The 30 mA Type A trip covers sinusoidal AC and pulsating DC residual currents — the standard for general-purpose socket-outlet and lighting circuits in residential and commercial panels. The 100 A rated current at AC (derated to 93 A at 40 °C, 80 A at 70 °C) matches the main incoming supply for a typical distribution board; the derating curve lets you size for elevated ambient temperatures inside a sealed enclosure. Insulation voltage rated 460 V and overvoltage category III mean the device is suitable for fixed-installation downstream of the utility meter. Surge current resistance of 1 kA and surge voltage resistance of 4 kV give it a solid margin for transient events on the mains. The IP20 rating applies only when the board is installed and conductors are connected — it is not a standalone outdoor device. The top-or-bottom feed position gives flexibility in panel layout.","metaTitle":"Siemens 5SM2327-6 SENTRON RCD, 2-pole, 100 A, 30 mA, Type A","metaDescription":"Siemens 5SM2327-6 SENTRON 2-pole RCD, 100 A rated, 30 mA Type A, instantaneous. Current lifecycle stage. Quoted to order against RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Residual Current Breakers (RCCB/RCBO)"],"specifications":{"Depth":"70 mm","Width":"71 mm","title":"5SM2327-6","Height":"90 mm","Maximum":"75 °C","Minimum":"-40 °C","Sealable":"No","description":"RC unit for 5SP4, 2-pole, type A, In: 100 A, 30 mA, Un AC: 230 V","Design Of Pole":"2 poles","Number Of Poles":"2","lifecycle_stage":"current","Fastening Method":"REG","Mounting Position":"any","at AC rated value":"100 A","Installation Depth":"70 mm","Product Brand Name":"SENTRON","Product Variations":"for 5SP4","Degree Of Pollution":"2","Product Designation":"RCD-unit","protection class IP":"IP20, if the distribution board is installed, with connected conductors","Overvoltage Category":"III","Design Of The Product":"instantaneous","Residual Current Type":"A","at 40 °C rated value":"93 A","at 45 °C rated value":"93 A","at 50 °C rated value":"90 A","at 55 °C rated value":"87 A","at 60 °C rated value":"85 A","at 65 °C rated value":"83 A","at 70 °C rated value":"80 A","OFF-delay time adjustable":"No","For Testing Equipment Minimum":"195 V","Number Of Modular Width Units":"4","Position Of Power Supply Cord":"top or bottom","Rated Fault Current Adjustable":"No","Protection Function False Tripping":"Yes","Tripping Fault Current Rated Value":"30 mA","insulation voltage (Ui) rated value":"460 V","Surge Current Resistance Rated Value":"1 kA","Surge Voltage Resistance Rated Value":"4 000 V","Value Range Of The Operating Frequency":"50 Hz","reference code according to IEC 81346-2":"F","Type Of Voltage Of The Operating Voltage":"AC","Value Range Of The Supply Voltage Frequency":"50 Hz","Mechanical Service Life (Operating Cycles) Typical":"10 000","for rated value of the current at AC in hot operating state per pole":"6 W"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"stockQuantity":0,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/4da40b2d23f6aa0c08c20418984a19f6.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=428380&mlfb=5SM2327-6"},"ai":{"faq":[{"question":"What is the tripping fault current of 5SM2327-6?","answer":"The rated tripping fault current is 30 mA, Type A (sinusoidal AC and pulsating DC)."},{"question":"What is the rated current of 5SM2327-6?","answer":"The rated current is 100 A at AC, derated at higher ambient temperatures (93 A at 40 °C, 80 A at 70 °C)."},{"question":"Where can I buy 5SM2327-6?","answer":"The part is sourced and quoted to order against an RFQ through independent distribution; availability and current pricing are confirmed at quote time."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"icboms-matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/5SM2327-6","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/5SM2327-6 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-08-11T15:51:03.652Z","lastPublished":"2026-08-11T15:51:03.652Z","indexable":true}}