{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"5SM2332-0","brand":"Siemens","brandSlug":"siemens","productSlug":"5SM2332-0","canonicalUrl":"https://aoctrl.com/siemens/5SM2332-0","factsUrl":"https://aoctrl.com/api/mcp/products/5SM2332-0","rawCanonicalId":null},"summary":{"shortDescription":"SENTRON 5SM2332-0, RC unit for 5SY, 3-pole, type AC, In: 40 A, 30 mA, Un AC: 400 V.","salesMarkdown":"The SENTRON 5SM2332-0 is a 3-pole residual current device (RCD) unit designed for use with 5SY miniature circuit breakers. The RCD unit integrates with a 5SY MCB to form a combined RCBO assembly — supply can enter from top or bottom. IP20 rated when installed in a distribution board with conductors connected. Temperature derating applies: at 40 °C the rated current drops to 37.2 A, at 50 °C to 36 A, at 60 °C to 34 A, and at 70 °C to 32 A. The unit is not sealable and has no adjustable delay or adjustable fault current.","metaTitle":"SENTRON 5SM2332-0 RCD Unit, 40 A, 30 mA, 3-pole","metaDescription":"SENTRON 5SM2332-0 RCD unit for 5SY, 3-pole, type AC, 40 A rated current, 30 mA trip, 400 V AC. Current lifecycle stage. Sourced to order against RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Residual Current Breakers (RCCB/RCBO)"],"specifications":{"title":"5SM2332-0","Maximum":"75 °C","Minimum":"-40 °C","Sealable":"No","description":"RC unit for 5SY, 3-pole, type AC, In: 40 A, 30 mA, Un AC: 400 V","Design Of Pole":"3 poles","Number Of Poles":"3","lifecycle_stage":"current","Fastening Method":"REG","Mounting Position":"any","at AC rated value":"40 A","Installation Depth":"70 mm","Product Brand Name":"SENTRON","Product Variations":"for 5SY","Degree Of Pollution":"2","Product Designation":"RCD-unit","protection class IP":"IP20, if the distribution board is installed, with connected conductors","Overvoltage Category":"III","Design Of The Product":"instantaneous","Residual Current Type":"AC","at 40 °C rated value":"37.2 A","at 45 °C rated value":"37.2 A","at 50 °C rated value":"36 A","at 55 °C rated value":"34.8 A","at 60 °C rated value":"34 A","at 65 °C rated value":"33.2 A","at 70 °C rated value":"32 A","OFF-delay time adjustable":"No","For Testing Equipment Minimum":"195 V","Number Of Modular Width Units":"3","Position Of Power Supply Cord":"top or bottom","Rated Fault Current Adjustable":"No","Protection Function False Tripping":"Yes","Tripping Fault Current Rated Value":"30 mA","insulation voltage (Ui) rated value":"460 V","Surge Voltage Resistance Rated Value":"4 000 V","Value Range Of The Operating Frequency":"50 Hz","Type Of Voltage Of The Operating Voltage":"AC","Value Range Of The Supply Voltage Frequency":"50 Hz","Mechanical Service Life (Operating Cycles) Typical":"10 000","for rated value of the current at AC in hot operating state per pole":"3.6 W"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"stockQuantity":0,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/6e7894eb94382bc02f37d1cdf3fce33b.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=235359&mlfb=5SM2332-0"},"ai":{"faq":[],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"icboms-matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/5SM2332-0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/5SM2332-0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-08-11T15:51:03.652Z","lastPublished":"2026-08-11T15:51:03.652Z","indexable":true}}