{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"5SM2335-6","brand":"Siemens","brandSlug":"siemens","productSlug":"5SM2335-6","canonicalUrl":"https://aoctrl.com/siemens/5SM2335-6","factsUrl":"https://aoctrl.com/api/mcp/products/5SM2335-6","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON, RCD-unit, 5SM2335-6, 3-pole, 63 A AC rated, 30 mA Type A, instantaneous, 50 Hz, IP20, 3 MW wide.","salesMarkdown":"## RCD for panel builders: what the ratings mean The 63 A AC rated current at 50 Hz is the continuous load it carries; above 40 °C ambient, the derating curve applies: 58.6 A at 40 °C, stepping down to 50.4 A at 70 °C. Instantaneous tripping with no adjustable time delay (OFF-delay not adjustable) means it responds to the first fault cycle — suited for shock protection, not selective coordination. The surge current resistance is rated 1 kA, surge voltage resistance 4 kV, giving it a solid margin against switching transients common in motor control panels. Occupies 3 modular width units (MW) on a DIN rail. Depth is 70 mm, width 107 mm, height 90 mm. Fastening method is REG (regular DIN-rail clip). Mounting position any — no restriction on orientation. Rated IP20 only when the distribution board is installed and conductors are connected — this is an enclosed-panel component, not a standalone enclosure. Sealable? No. That means no provision for a lead-seal wire through the actuator — relevant if your site requires tamper-evident locking on the RCD handle. Lifecycle stage is current — this is an active, in-production Siemens SENTRON catalog item.","metaTitle":"Siemens 5SM2335-6 SENTRON RCD, 63A 30mA Type A, 3-pole","metaDescription":"Siemens 5SM2335-6 SENTRON RCD unit, 63 A rated, 30 mA Type A residual current, 3-pole, IP20. Current lifecycle status. Sourced to order against RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Residual Current Breakers (RCCB/RCBO)"],"specifications":{"Depth":"70 mm","Width":"107 mm","title":"5SM2335-6","Height":"90 mm","Maximum":"75 °C","Minimum":"-40 °C","Sealable":"No","description":"RC unit for 5SY, 3-pole, type A, In: 63 A, 30 mA, Un AC: 400 V","Design Of Pole":"3 poles","Number Of Poles":"3","lifecycle_stage":"current","Fastening Method":"REG","Mounting Position":"any","at AC rated value":"63 A","Installation Depth":"70 mm","Product Brand Name":"SENTRON","Product Variations":"for 5SY","Degree Of Pollution":"2","Product Designation":"RCD-unit","protection class IP":"IP20, if the distribution board is installed, with connected conductors","Overvoltage Category":"III","Design Of The Product":"instantaneous","Residual Current Type":"A","at 40 °C rated value":"58.6 A","at 45 °C rated value":"58.59 A","at 50 °C rated value":"56.7 A","at 55 °C rated value":"54.81 A","at 60 °C rated value":"53.55 A","at 65 °C rated value":"52.29 A","at 70 °C rated value":"50.4 A","OFF-delay time adjustable":"No","For Testing Equipment Minimum":"195 V","Number Of Modular Width Units":"3","Position Of Power Supply Cord":"top or bottom","Rated Fault Current Adjustable":"No","Protection Function False Tripping":"Yes","Tripping Fault Current Rated Value":"30 mA","insulation voltage (Ui) rated value":"460 V","Surge Current Resistance Rated Value":"1 kA","Surge Voltage Resistance Rated Value":"4 000 V","Value Range Of The Operating Frequency":"50 Hz","reference code according to IEC 81346-2":"F","Type Of Voltage Of The Operating Voltage":"AC","Value Range Of The Supply Voltage Frequency":"50 Hz","Mechanical Service Life (Operating Cycles) Typical":"10 000","for rated value of the current at AC in hot operating state per pole":"4.6 W"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"stockQuantity":0,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/f5a66cf669727ed26baefc7cefc66e5b.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=263711&mlfb=5SM2335-6"},"ai":{"faq":[{"question":"What is the 5SM2335-6 depth and width?","answer":"Depth is 70 mm, width is 107 mm, height is 90 mm. It occupies 3 modular width units on a DIN rail."},{"question":"What does Type A residual current mean on this RCD?","answer":"Type A detects sinusoidal AC and pulsating DC fault currents — the standard choice for panels with electronics, VFDs, or single-phase rectifiers that generate pulsed DC leakage."},{"question":"Does the 5SM2335-6 have an adjustable trip delay?","answer":"No — it is an instantaneous RCD with no adjustable OFF-delay time and no adjustable rated fault current. Trips on the first fault cycle."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"icboms-matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/5SM2335-6","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/5SM2335-6 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-08-11T15:51:03.652Z","lastPublished":"2026-08-11T15:51:03.652Z","indexable":true}}