{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"5SM2845-2","brand":"Siemens","brandSlug":"siemens","productSlug":"5SM2845-2","canonicalUrl":"https://aoctrl.com/siemens/5SM2845-2","factsUrl":"https://aoctrl.com/api/mcp/products/5SM2845-2","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 5SM2845-2, selective RCD unit for 5SY, 4-pole, type AC, In: 63 A, IΔn: 1000 mA, Un AC: 400 V.","salesMarkdown":"The Siemens 5SM2845-2 is a 4-pole selective residual-current device (RCD) from the SENTRON series, designed as an add-on unit for the 5SY miniature circuit breaker range. Selective design (type S) means it incorporates a short time delay so that downstream RCDs trip first during a fault, keeping this unit as the backup — critical for panel coordination in distribution boards where you want only the branch circuit to drop, not the whole submain. Rated at 63 A continuous. The 1000 mA residual trip threshold is for fire or equipment protection, not personnel protection. Rated insulation voltage (Ui) is 460 V, surge voltage resistance is 4 kV, and overvoltage category III — all consistent with 400 V three-phase distribution panels where it's installed downstream of the main switch. The IP20 rating (with conductors connected, in an installed distribution board) is standard for enclosed panel mount — no washdown rating here. Occupies 4 modular width units. Installation depth is 70 mm. Designed as a clip-on RCD unit for the 5SY MCB series — it's not a standalone device; it mounts to the right of the corresponding 5SY breaker and connects via the busbar and a mechanical trip link. If you're replacing a failed unit in an existing 5SY panel, this drops in without rewiring the load side. The OFF-delay is not adjustable, and the rated fault current is fixed at 1000 mA — no field tweaks. False-tripping protection is built in (suppression of nuisance trips from transient surges).","metaTitle":"Siemens 5SM2845-2 SENTRON RCD Unit, 63A 1000mA AC Selective","metaDescription":"Siemens 5SM2845-2 SENTRON selective RCD unit, 4-pole, type AC, 63 A rated current, 1000 mA fault current, 400 V AC. Current lifecycle stage, sourced to order. Request quote.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":[],"specifications":{"Poles":"4","Mounting":"REG","Product Status":"Active"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/ed6c9ae46f38f3bdf200f92fe55a2666.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=127599&mlfb=5SM2845-2","alternativesUrl":"https://aoctrl.com/api/mcp/products/5SM2845-2/alternatives.json"},"ai":{"faq":[],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/5SM2845-2","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/5SM2845-2 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}