{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"5SM3616-6KL01","brand":"Siemens","brandSlug":"siemens","productSlug":"5SM3616-6KL01","canonicalUrl":"https://aoctrl.com/siemens/5SM3616-6KL01","factsUrl":"https://aoctrl.com/api/mcp/products/5SM3616-6KL01","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 5SM3 series RCCB, 2-pole, Type A, short-time delayed, 63 A rated, 300 mA trip, 230 V AC, 50 Hz, DIN rail mount.","salesMarkdown":"The Siemens 5SM3616-6KL01 is a 2-pole residual current circuit breaker (RCCB) from the SENTRON 5SM3 series, rated 63 A at 230 V AC, 50 Hz, with a 300 mA trip threshold and Type A fault current sensitivity. The short-time delayed design means it tolerates brief surge currents up to 3 kA without nuisance tripping — useful on circuits with motor drives or switching power supplies that generate a short inrush. Mounts on DIN rail (REG) and occupies 2.5 width units (36 mm wide, 90 mm high, 70 mm deep). The screw terminals accept solid or stranded copper from 1.5 to 25 mm²; tighten to 2.5–3 N·m. Supply can land top or bottom. The N-left variant places the neutral on the left side — check your busbar orientation before wiring. IP20 with the distribution board closed and conductors connected; not rated for wet or washdown environments.","metaTitle":"Siemens 5SM3616-6KL01 SENTRON RCCB, 63 A, 300 mA, 2-pole","metaDescription":"Siemens SENTRON 5SM3616-6KL01 RCCB, 2-pole Type A short-time delayed, 63 A / 300 mA, 230 V AC, 50 Hz. DIN rail mount. Current lifecycle. Quoted to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Residual Current Breakers (RCCB/RCBO)"],"specifications":{"Depth":"70 mm","Solid":"1.5 ... 25 mm²","Width":"36 mm","Height":"90 mm","Stranded":"1.5 ... 25 mm²","Rated Value":"50 Hz","Mounting type":"DIN rail (REG)","During Storage":"-40 ... +75 °C","Number of poles":"2","lifecycle_stage":"current","Mounting position":"any","Installation depth":"70 mm","Product brand name":"SENTRON","Product variations":"N left","Ambient temperature":"-25 ... +45 °C","Operating frequency":"50Hz","Product designation":"RCCB","Protection class IP":"IP20, if the distribution board is installed, with connected conductors","Overvoltage category":"III","Design of the product":"Short-time delayed","Number of width units":"2.5","Type of fault current":"A","acc. to DIN EN 61346-2":"F","acc. to DIN EN 81346-2":"F","circuit-breaker / Design":"5SM3","Current / at AC / rated value":"63 A","Product feature / silicon-free":"Yes","Position / of power supply cord":"top or bottom","Protection against electrical shock":"Finger and back-of-hand safe","Supply voltage / at AC / rated value":"230 V","Surge current resistance / rated value":"3 kA","Switching function / short-term delayed":"Yes","Tripping residual current / rated value":"300 mA","Tightening torque / with screw-type terminals":"2.5 ... 3 N·m","Size of installation devices / acc. to DIN 43880":"1","Supply voltage / for testing equipment / minimum":"100 V","Mechanical service life (switching cycles) / typical":"10 000"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=348641&mlfb=5SM3616-6KL01","alternativesUrl":"https://aoctrl.com/api/mcp/products/5SM3616-6KL01/alternatives.json"},"ai":{"faq":[{"question":"Where can I buy 5SM3616-6KL01 and how do I get a price?","answer":"Sourced and quoted to order against an RFQ through independent distribution; availability and current pricing are confirmed at quote time."},{"question":"What is 5SM3616-6KL01's listed depth?","answer":"The installation depth is 70 mm."},{"question":"What wire sizes does 5SM3616-6KL01 accept?","answer":"The screw terminals accept solid or stranded copper from 1.5 to 25 mm²."},{"question":"What does Type A fault current mean on this RCCB?","answer":"Type A detects sinusoidal AC and pulsating DC fault currents, covering most modern electronic loads like rectifiers and switching power supplies."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/5SM3616-6KL01","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/5SM3616-6KL01 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}