{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"5SM3617-0","brand":"Siemens","brandSlug":"siemens","productSlug":"5SM3617-0","canonicalUrl":"https://aoctrl.com/siemens/5SM3617-0","factsUrl":"https://aoctrl.com/api/mcp/products/5SM3617-0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 5SM3617-0 RCCB, 80 A at 40 °C, 2-pole, AC type, 230 V, 10 kA, DIN rail mount, instantaneous.","salesMarkdown":"The Siemens 5SM3617-0 is a SENTRON residual current circuit breaker (RCCB), 2-pole, AC type, rated 80 A at 40 °C and 230 V supply. Instantaneous tripping, no short-time delay. Mounts on DIN rail (REG), occupies 2.5 width units (36 mm). IP20 with distribution board installed and conductors connected. 80 A at 40 °C is the headline rating — derate linearly above that: 76.8 A at 50 °C, 73.6 A at 55 °C, 70.4 A at 60 °C, 67.2 A at 65 °C, 64 A at 70 °C. Short-circuit current rating (SCCR) is 10 kA per IEC 61008-1. The EN 60898 rating is lower at 0.8 kA, which governs the conditional rating for back-up fuse coordination. Not suitable for pulsating DC or smooth DC faults (those need A or B type). Finger and back-of-hand safe per the protection-against-shock feature — that's a panel-builder consideration for live-bus exposure. ## Deployment context DIN-rail snap-on, any mounting position. Supply cord can land top or bottom — no orientation restriction. 70 mm installation depth fits standard 70 mm deep enclosures. Silicon-free construction matters for coating/adhesion-sensitive environments (conformal coating lines, potting).","metaTitle":"Siemens 5SM3617-0 SENTRON RCCB, 80A 2P AC, 230V, 10kA","metaDescription":"Siemens 5SM3617-0 SENTRON RCCB, 80A rated at 40 °C, 2-pole, AC type, 230 V, 10 kA SCCR. Active production. Quoted to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Residual Current Breakers (RCCB/RCBO)"],"specifications":{"Depth":"70 mm","Width":"36 mm","Height":"90 mm","Maximum":"45 °C","Minimum":"-5 °C","Rated Value":"50 Hz","Mounting Type":"DIN rail (REG)","Number Of Poles":"2","lifecycle_stage":"current","Mounting Position":"any","Installation Depth":"70 mm","Product Brand Name":"SENTRON","Maximum Permissible":"75 °C","Minimum Permissible":"-40 °C","Operating Frequency":"50 Hz","Product Designation":"RCCB","protection class IP":"IP20, if the distribution board is installed, with connected conductors","Overvoltage Category":"III","Design Of The Product":"Instantaneous","Number Of Width Units":"2.5","Type Of Fault Current":"AC","acc. to DIN EN 61346-2":"F","acc. to DIN EN 81346-2":"F","I2t value / permissible":"70 000 A²·s","at 40 °C / rated value":"80 A","at 45 °C / rated value":"80 A","at 50 °C / rated value":"76.8 A","at 55 °C / rated value":"73.6 A","at 60 °C / rated value":"70.4 A","at 65 °C / rated value":"67.2 A","at 70 °C / rated value":"64 A","Short-Circuit Current Rating":"10 kA","Product Feature / Silicon-Free":"Yes","acc. to EN 60898 / rated value":"0.8 kA","Position / Of Power Supply Cord":"top or bottom","Let-Through Current / Permissible":"7 500 kA","Protection Against Electrical Shock":"Finger and back-of-hand safe","supply voltage / at AC / rated value":"230 V","according to IEC 61008-1 / rated value":"0.8 kA","Switching Function / Short-Term Delayed":"No","Tripping Residual Current / Rated Value":"300 mA","operating current / at AC / rated value":"80 A","Supply Voltage / For Testing Equipment / Minimum":"100 V","size of installation devices / acc. to DIN 43880":"1","Mechanical Service Life (Switching Cycles) / Typical":"10 000"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=54860&mlfb=5SM3617-0","alternativesUrl":"https://aoctrl.com/api/mcp/products/5SM3617-0/alternatives.json"},"ai":{"faq":[{"question":"What are the key ratings of the 5SM3617-0?","answer":"80 A at 40 °C, 2-pole, AC type, 230 V, 10 kA SCCR, instantaneous trip. DIN rail mount, 2.5 width units (36 mm wide)."},{"question":"Will the 5SM3617-0 drop into a panel specified around the 5SU9354-7KK16?","answer":"Both are 2-pole, DIN-rail RCCBs, but the 5SU9354-7KK16 is a different series with its own rating profile. The 5SM3617-0 is 80 A, AC type, instantaneous — verify the existing panel's rated current, fault type, and coordination before swapping without rewiring."},{"question":"How do I get current pricing and availability for the 5SM3617-0?","answer":"Sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing confirmed at quote time."},{"question":"What compliance documentation does Siemens provide for the 5SM3617-0?","answer":"The part carries IEC 61008-1 and EN 60898 ratings. Silicon-free declared. Specific RoHS/REACH/UL declarations are manufacturer-supplied with the shipment; request them at order time."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/5SM3617-0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/5SM3617-0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}