{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"5SM3617-6","brand":"Siemens","brandSlug":"siemens","productSlug":"5SM3617-6","canonicalUrl":"https://aoctrl.com/siemens/5SM3617-6","factsUrl":"https://aoctrl.com/api/mcp/products/5SM3617-6","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 5SM3617-6, RCCB, 2-pole, 80 A, Type A, 10 kA, 230 V AC, DIN rail mount.","salesMarkdown":"The 5SM3617-6: 80 A at 40 °C ambient, derated to 64 A at 70 °C — that's the continuous current it can carry without nuisance tripping. Type A detection catches pulsating DC fault currents (common from rectified loads like VFDs, LED drivers, or switching power supplies) plus the usual sinusoidal AC — so it's the right choice for mixed-load panels where a plain AC-type RCCB would miss half the fault signature. The 2-pole form factor snaps onto a DIN rail (REG mounting), occupies 2.5 width units (about 45 mm), and accepts conductors from 1.5 to 25 mm² solid or stranded. That's enough cross-section for the full 80 A feed without needing a separate terminal adapter. ## Deployment context The finger and back-of-hand safe design means you can work in the panel with the cover off without risking contact with live busbars.","metaTitle":"Siemens 5SM3617-6 SENTRON RCCB, 80 A, 2-Pole, Type A, 10 kA","metaDescription":"Siemens 5SM3617-6 SENTRON RCCB, 80 A, 2-pole, Type A, 10 kA short-circuit rating, 230 V AC. Current production. Sourced to order against RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Residual Current Breakers (RCCB/RCBO)"],"specifications":{"Depth":"70 mm","Solid":"1.5 ... 25 mm²","Width":"36 mm","Height":"90 mm","Stranded":"1.5 ... 25 mm²","at 40 Cel":"80 A","at 45 Cel":"80 A","at 50 Cel":"76.8 A","at 55 Cel":"73.6 A","at 60 Cel":"70.4 A","at 65 Cel":"67.2 A","at 70 Cel":"64 A","Rated Value":"50 Hz","Wertebereich":"-25 ... +45 °C","Mounting type":"DIN rail (REG)","Number of poles":"2","lifecycle_stage":"current","Mounting position":"any","Installation depth":"70 mm","Product brand name":"SENTRON","Ambient temperature":"-40 ... +75 °C","Operating frequency":"50Hz","Product designation":"RCCB","Protection class IP":"IP20, if the distribution board is installed, with connected conductors","Overvoltage category":"III","Design of the product":"Instantaneous","Number of width units":"2.5","Type of fault current":"A","acc. to DIN EN 61346-2":"F","acc. to DIN EN 81346-2":"F","I2t-value / permissible":"70 000 A²·s","circuit-breaker / Design":"5SM3","Short-circuit current rating":"10 kA","Current / at AC / rated value":"80 A","Product feature / silicon-free":"Yes","Position / of power supply cord":"top or bottom","Protection against electrical shock":"Finger and back-of-hand safe","Supply voltage / at AC / rated value":"230 V","Surge current resistance / rated value":"1 kA","Switching function / short-term delayed":"No","Tripping residual current / rated value":"300 mA","Tightening torque / with screw-type terminals":"2.5 ... 3 N·m","Size of installation devices / acc. to DIN 43880":"1","Supply voltage / for testing equipment / minimum":"100 V","Mechanical service life (switching cycles) / typical":"10 000"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":"$171.45","priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=134713&mlfb=5SM3617-6","alternativesUrl":"https://aoctrl.com/api/mcp/products/5SM3617-6/alternatives.json"},"ai":{"faq":[{"question":"What is 5SM3617-6's listed depth (70 mm) on this component line?","answer":"The depth is 70 mm, which is the standard depth for this SENTRON RCCB series — it fits most DIN-rail enclosures with a 70 mm or deeper gland plate clearance."},{"question":"What compliance documentation does this brand provide for 5SM3617-6 (RoHS, REACH, UL, IEC)?","answer":"The product carries the SENTRON brand and is designed to IEC/EN standards (overvoltage category III, 10 kA SCCR). The evidence does not list specific RoHS/REACH/UL declarations, but Siemens typically provides a Declaration of Conformity and material compliance data on request — include that in your RFQ."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/5SM3617-6","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/5SM3617-6 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}