{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"5SN6010-7CN","brand":"Siemens","brandSlug":"siemens","productSlug":"5SN6010-7CN","canonicalUrl":"https://aoctrl.com/siemens/5SN6010-7CN","factsUrl":"https://aoctrl.com/api/mcp/products/5SN6010-7CN","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 5SN6010-7CN, miniature circuit breaker compact, 1P+N, 10 A, C-characteristic, 6 kA acc. to EN 60898, 1 MW, IP20.","salesMarkdown":"At 40 °C it derates to 9.5 A, and at 45 °C to 9.3 A — so a panel running warm near the top of a DB may need to step up one frame size if the continuous load is close to 10 A. Insulation voltage is 250 V AC, with a maximum operating voltage of 250 V for single-phase operation. Mounting position is any orientation — no derating needed for horizontal or inverted fit. The neutral pole switches internally, so no separate neutral bar is required for the outgoing circuit. Touch protection is built in; IP20 rating applies with connected conductors. Current-production part in the SENTRON portfolio. The 5SN6010-7CN is specified into new BOMs and stocked for MRO spares. Halogen-free and silicon-free construction — important for installations where outgassing could affect sensitive contacts or electronics. Vibration-resistant per IEC 60068-2-6. Ambient operating range covers -25 °C to +60 °C with humidity limits (85% rF up to 45 °C, 43% rF above). Energy limitation class 3 means it lets through less energy during a fault than class 1 or 2 devices, reducing stress on downstream components.","metaTitle":"Siemens 5SN6010-7CN SENTRON MCB, 10A 1P+N C-Curve","metaDescription":"Siemens 5SN6010-7CN SENTRON miniature circuit breaker, 10A rated, 6kA breaking capacity, C-curve, 1P+N, 1MW, IP20. Quoted to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["1-Pole MCB (DIN Rail)"],"specifications":{"Depth":"76 mm","Width":"18 mm","Height":"90 mm","Maximum":"75 °C","Minimum":"-40 °C","Sealable":"Yes","Halogen-Free":"Yes","Silicon-Free":"Yes","Design Of Pole":"1P+N","lifecycle_stage":"current","Fastening Method":"standard rail","Mounting Position":"any","Installation Depth":"70 mm","Product Brand Name":"SENTRON","Degree Of Pollution":"2","Product Designation":"Miniature circuit breaker","acc. to IEC 81346-2":"F","at AC / rated value":"10 A","protection class IP":"IP20, with connected conductors","Overvoltage Category":"III","Combined Terminal Top":"No","Design Of The Product":"Miniature circuit breaker compact","acc. to DIN EN 61346-2":"F","Energy Limitation Class":"3","at 30 °C / rated value":"10 A","at 40 °C / rated value":"9.5 A","at 45 °C / rated value":"9.3 A","Combined Terminal Bottom":"No","Suitability For Operation":"Residential buildings/infrastructure","Number Of Modular Width Units":"1","Tripping Characteristic Class":"C","acc. to EN 60898 / rated value":"6 kA","Position / Of Power Supply Cord":"Any","Product Feature / Touch Protection":"Yes","Ambient Temperature / During Operation":"-25...45°C: max. 85%rF, 45 60°C: max. 43%rF","Type Of Voltage / Of The Operating Voltage":"AC","vibration resistance / acc. to IEC 60068-2-6":"Yes","insulation voltage (Ui) / at AC / rated value":"250 V","with single-phase operation / at AC / maximum":"250 V","Product Component / Neutral Conductor Switching":"Yes","Mechanical Service Life (Switching Cycles) / Typical":"10 000"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/8c5c99293ebcb7bc713e04ffcffd537b.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=572160&mlfb=5SN6010-7CN","alternativesUrl":"https://aoctrl.com/api/mcp/products/5SN6010-7CN/alternatives.json"},"ai":{"faq":[{"question":"What is the breaking capacity of 5SN6010-7CN?","answer":"6 kA per EN 60898, suitable for residential and light-commercial final subcircuits."},{"question":"Will 5SN6010-7CN drop into a panel specified around 5SL6120-7?","answer":"Both are 1-module-wide Siemens MCBs on standard DIN rail, so the mechanical fit is the same. However, the 5SL6120-7 is a 20 A B-curve device; the 5SN6010-7CN is 10 A C-curve — verify the load and coordination requirements before swapping."},{"question":"Where can I buy 5SN6010-7CN and how is it quoted?","answer":"Sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing confirmed at quote time."},{"question":"What compliance documentation does Siemens provide for 5SN6010-7CN?","answer":"The part carries EN 60898 rating for breaking capacity, IEC 60068-2-6 vibration resistance, and is halogen-free and silicon-free. Standard Siemens declarations for RoHS and REACH are available on request."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/5SN6010-7CN","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/5SN6010-7CN when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}