{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"5SN6106-7CN","brand":"Siemens","brandSlug":"siemens","productSlug":"5SN6106-7CN","canonicalUrl":"https://aoctrl.com/siemens/5SN6106-7CN","factsUrl":"https://aoctrl.com/api/mcp/products/5SN6106-7CN","rawCanonicalId":null},"summary":{"shortDescription":"SENTRON 5SN6106-7CN miniature circuit breaker, 1-pole, C-curve, 6 A, 6 kA per EN 60898, 230/400 V AC, 1 MW unit, IP20.","salesMarkdown":"The SENTRON 5SN6106-7CN is a 1-pole miniature circuit breaker (MCB) with a C tripping characteristic, rated 6 A at 30 °C and breaking 6 kA per EN 60898 at 230/400 V AC. At 40 °C the continuous rating derates to 5.53 A, at 50 °C to 5.02 A, and at 55 °C to 4.75 A; if the panel ambient runs hot, size up or accept the lower headroom. Single-phase it handles 250 V AC; multi-phase operation (two or three poles ganged) is rated 440 V AC maximum. DC rating tops out at 72 V — fine for control-voltage DC bus work but not for a 125 V DC battery bank. Mounting position is unrestricted — vertical, horizontal, or upside-down on the rail, the breaker operates the same. Touch protection is built in; no separate finger-safe shrouds needed.","metaTitle":"5SN6106-7CN SENTRON MCB, 1-pole, C-curve, 6A, 6kA","metaDescription":"SENTRON 5SN6106-7CN miniature circuit breaker, 1-pole, C-curve, 6A, 6kA per EN 60898. Current production. Quoted to order against RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["1-Pole MCB (DIN Rail)"],"specifications":{"Depth":"76 mm","Width":"18 mm","title":"5SN6106-7CN","Height":"90 mm","Maximum":"75 °C","Minimum":"-40 °C","Sealable":"Yes","description":"Circuit breaker 230/400V, 6kA, 1-pole, C, 6A","Halogen-Free":"Yes","Silicon-Free":"Yes","Number Of Poles":"1","lifecycle_stage":"current","Mounting Position":"any","Installation Depth":"70 mm","Product Brand Name":"SENTRON","Degree Of Pollution":"2","Product Designation":"Miniature circuit breaker","acc. to IEC 81346-2":"F","at AC / rated value":"6 A","protection class IP":"IP20, with connected conductors","Overvoltage Category":"III","acc. to DIN EN 61346-2":"F","Energy Limitation Class":"3","at 30 °C / rated value":"6 A","at 40 °C / rated value":"5.53 A","at 45 °C / rated value":"5.28 A","at 50 °C / rated value":"5.02 A","at 55 °C / rated value":"4.75 A","Number Of Modular Width Units":"1","Tripping Characteristic Class":"C","at DC / rated value / maximum":"72 V","acc. to EN 60898 / rated value":"6 kA","Product Feature / Touch Protection":"Yes","supply voltage / at AC / rated value":"400 V","Influence Of The Surrounding Temperature":"Periodically +55°C, max. 95% humidity","vibration resistance / acc. to IEC 60068-2-6":"50 m/s² at 25 to 150 Hz","with multi-phase operation / at AC / maximum":"440 V","Product Function / Neutral Conductor Switching":"No","with multi-phase operation / at AC / rated value":"440 V","with single-phase operation / at AC / rated value":"250 V"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"stockQuantity":0,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/7e2aa06e5a73d3458fe006a1800c9bef.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=24268&mlfb=5SN6106-7CN"},"ai":{"faq":[{"question":"Where can I buy 5SN6106-7CN and how do I get a price?","answer":"Sourced and quoted to order against an RFQ through independent distribution. Submit a request for quote; availability and current pricing are confirmed at quote time."},{"question":"Will 5SN6106-7CN drop into a panel specified around 5SL6006-7 without rewiring?","answer":"Yes — both are 1 MW (18 mm) DIN-rail MCBs with the same clip and busbar pitch. The 5SN is the current SENTRON series replacing the 5SL; no rewiring needed for the swap."},{"question":"What is the depth of 5SN6106-7CN?","answer":"76 mm overall depth, with an installation depth of 70 mm behind the panel face."},{"question":"What compliance documentation does SENTRON provide for 5SN6106-7CN?","answer":"The breaker is rated per EN 60898 for breaking capacity, carries overvoltage category III and pollution degree 2, and is halogen-free and silicon-free. RoHS and REACH declarations are standard for the SENTRON line; request them with the RFQ."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"icboms-matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/5SN6106-7CN","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/5SN6106-7CN when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-08-11T15:51:03.652Z","lastPublished":"2026-08-11T15:51:03.652Z","indexable":true}}