{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"5SP3716-2KK02","brand":"Siemens","brandSlug":"siemens","productSlug":"5SP3716-2KK02","canonicalUrl":"https://aoctrl.com/siemens/5SP3716-2KK02","factsUrl":"https://aoctrl.com/api/mcp/products/5SP3716-2KK02","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 5SP3 series, main miniature circuit breaker (SHU), 1-pole, 16 A, E tripping characteristic, 230/400 V AC, 25 kA breaking capacity per EN 60898, busbar mount.","salesMarkdown":"The Siemens 5SP3716-2KK02 is a 1-pole main miniature circuit breaker (SHU) from the SENTRON 5SP3 series, rated 16 A with an E tripping characteristic at 230/400 V AC, 50 Hz. Mounts on a 40-mm busbar system per DIN 43870 Part 2. The 1.5 width units and 89.5 mm depth fit the lower section of a meter panel. That's high for a 1-pole 16 A device; it's sized for the high fault levels at the incoming side of a meter panel, not a sub-distribution board. The 6 kV rated surge voltage resistance (overvoltage category IV) confirms it's designed for the utility-side interface where lightning and switching surges hit hardest. The E tripping characteristic has a magnetic trip threshold higher than a C curve. This delays instantaneous tripping so a downstream MCB clears a fault first. Rated insulation voltage 690 V and pollution degree 3 mean it's suitable for the 230/400 V three-phase networks common in European infrastructure, even in dusty or conductive environments. The IP40 rating (with connected conductors) is typical for enclosed panel mounting — no special sealing needed inside a meter cabinet. Infeed is via box terminal at the top; outgoing feeder uses a spring-loaded terminal at the bottom. The switch position indicator shows OFF = green, ON = red — a quick visual check during commissioning or troubleshooting. The locking slide accepts a padlock, wire seal, cable ties, or Antilux seal for tamper-proof metering applications. Mechanical life is 20,000 switching cycles typical — fine for a main breaker that sees infrequent manual operation, not a daily-switched load. Shock resistance is 30 g for 11 ms, vibration 2 g per IEC 60068-2-6, so it holds up in transport and seismic zones.","metaTitle":"Siemens 5SP3716-2KK02 SENTRON MCB, 1P, 16A, E-Curve, 25kA","metaDescription":"Siemens 5SP3716-2KK02 SENTRON miniature circuit breaker, 1-pole, 16 A, E tripping characteristic, 25 kA breaking capacity per EN 60898. Active production. Quoted to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":[],"specifications":{"Depth":"89.5 mm","Poles":"1","Height":"151.3 mm","Mounting":"Busbar","IP Rating":"IP40","Product Status":"Active"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/50430d6c6fffc9515e0070c9e8dac7d4.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=217610&mlfb=5SP3716-2KK02","alternativesUrl":"https://aoctrl.com/api/mcp/products/5SP3716-2KK02/alternatives.json"},"ai":{"faq":[],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/5SP3716-2KK02","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/5SP3716-2KK02 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}