{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"5SQ2360-0KA13","brand":"Siemens","brandSlug":"siemens","productSlug":"5SQ2360-0KA13","canonicalUrl":"https://aoctrl.com/siemens/5SQ2360-0KA13","factsUrl":"https://aoctrl.com/api/mcp/products/5SQ2360-0KA13","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 5SQ2360-0KA13, 3-pole miniature circuit breaker, B tripping characteristic, 13 A rated current, 3 kA breaking capacity per EN 60898, 400 V AC, 50 Hz, IP20.","salesMarkdown":"The 5SQ2360-0KA13 is a 3-pole miniature circuit breaker rated 13 A at 400 V AC, 50 Hz, with a B tripping characteristic. Overvoltage category 3 and energy limiting class 3 align with distribution board use — it limits let-through energy for downstream equipment protection. ## Deployment context The 55 mm installation depth and 3 width units fit standard DIN-rail enclosures. The neutral conductor is not switched, so it's a 3-pole breaker for a 3-phase supply without neutral protection.","metaTitle":"SENTRON 5SQ2360-0KA13 Circuit Breaker, 3-Pole, B, 13A, 3kA","metaDescription":"Siemens SENTRON 5SQ2360-0KA13 miniature circuit breaker, 3-pole, B-curve, 13 A, 3 kA per EN 60898, 400 V AC, 50 Hz, IP20, current production. Sourced to order against RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Miniature Circuit Breakers (MCB)"],"specifications":{"Number of poles":"3","Type of voltage":"AC/DC","lifecycle_stage":"current","Installation depth":"55 mm","Product brand name":"SENTRON","Protection class IP":"IP20","Overvoltage category":"3","Energy limiting class":"3","Number of width units":"3","Number of poles / Note":"3P","circuit-breaker / Design":"5SQ","Current / at AC / rated value":"13 A","Tripping characteristic class":"B","acc. to EN 60898 / rated value":"3 kA","Supply voltage / at AC / rated value":"400 V","Supply voltage frequency / rated value":"50 Hz","Product function / neutral conductor switching":"No"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=320487&mlfb=5SQ2360-0KA13","alternativesUrl":"https://aoctrl.com/api/mcp/products/5SQ2360-0KA13/alternatives.json"},"ai":{"faq":[{"question":"What is the breaking capacity of 5SQ2360-0KA13?","answer":"3 kA per EN 60898 at 400 V AC."},{"question":"Will 5SQ2360-0KA13 drop into a panel specified around 5SQ2360-0KA16?","answer":"Yes — both are 3-pole, 55 mm deep, 3 width units, IP20, B-curve, 3 kA, 400 V AC, 50 Hz. The only difference is the current rating: 13 A vs 16 A. No rewiring needed if the load is within 13 A."},{"question":"Where can I buy 5SQ2360-0KA13?","answer":"This part is sourced to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/5SQ2360-0KA13","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/5SQ2360-0KA13 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}