{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"5SU1322-7KC25","brand":"Siemens","brandSlug":"siemens","productSlug":"5SU1322-7KC25","canonicalUrl":"https://aoctrl.com/siemens/5SU1322-7KC25","factsUrl":"https://aoctrl.com/api/mcp/products/5SU1322-7KC25","rawCanonicalId":null},"summary":{"shortDescription":"SENTRON 5SU1322-7KC25 RCBO, 2-pole, 25 A rated current, C tripping characteristic, 30 mA type A, 50 kA breaking capacity, 400 V AC, 50 Hz, instantaneous design, 2 width units, halogen-free and silicon-free, IP20 when installed.","salesMarkdown":"The 2-pole design switches both phase and neutral, so it's ready for single-phase sub-circuits in a 400 V AC, 50 Hz distribution board. Mounts in any position, takes 2 width units on the DIN rail, and its 70 mm installation depth fits standard enclosures. Conductor range covers 0.75 to 35 mm² solid or stranded, with screw terminals torqued to 2.5–3 N·m. At 25 A it'll hold a 5.5 kW motor start-up without nuisance tripping, but still clears a hard fault fast. The 30 mA type A residual detects pulsating DC fault currents — common on variable-frequency drives, LED drivers, and switched-mode supplies — which a plain AC type would miss. In a panel with a large upstream transformer, that's the difference between a coordinated trip and a cascade failure. The energy limiting class 3 rating tells you it restricts let-through energy to a low level, protecting downstream wiring and connected loads. Rated for ambient temperatures from -25 to +55 °C with up to 95% humidity, and storage from -40 to +75 °C. Overvoltage category III means it's designed for fixed-installation panels, not just socket-outlet circuits. The 1 kA surge current resistance (8/20 µs wave) handles lightning-induced transients typical in industrial buildings. Touch protection is built in (finger-safe terminals per the spec), which saves time on panel labeling and inspection sign-off.","metaTitle":"SENTRON 5SU1322-7KC25 RCBO, 2P, 25 A, C, 30 mA, 50 kA","metaDescription":"SENTRON 5SU1322-7KC25 RCBO, 2-pole, 25 A, C-curve, 30 mA type A, 50 kA breaking capacity. Current lifecycle stage. Quoted to order against RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":[],"specifications":{"Poles":"2","Product Status":"Active","Temp Operating Max":"55 °C","Temp Operating Min":"-25 °C"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/f8a3f804604e34cc21a3fa836405929c.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=3482&mlfb=5SU1322-7KC25","alternativesUrl":"https://aoctrl.com/api/mcp/products/5SU1322-7KC25/alternatives.json"},"ai":{"faq":[],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/5SU1322-7KC25","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/5SU1322-7KC25 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}