{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"5SU1324-6FA10","brand":"Siemens","brandSlug":"siemens","productSlug":"5SU1324-6FA10","canonicalUrl":"https://aoctrl.com/siemens/5SU1324-6FA10","factsUrl":"https://aoctrl.com/api/mcp/products/5SU1324-6FA10","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 5SU1324-6FA10 RCBO, 2-pole, 10 A rated at 30 °C, B tripping characteristic, 10 kA breaking capacity per EN 60898, 20 kA per IEC 60947-2, IP20, 77 mm depth.","salesMarkdown":"The B curve (3–5× In instantaneous trip) suits resistive and general-purpose loads; for motor or transformer inrush, a C or D curve would be the better fit. Depth is 77 mm, installation depth 70 mm — verify the enclosure depth before committing; a shallow consumer unit or compact distribution board may not close the cover with conductors dressed. IP20 only when the distribution board is installed and conductors are connected — not a standalone outdoor device. Supply can enter from top or bottom, which simplifies rework in existing panels. ## Thermal derating — the real-world rating At 40 °C it drops to 9.5 A, at 50 °C to 9 A, at 60 °C to 8.5 A, and at 70 °C to 7.7 A. Marked as current production.","metaTitle":"Siemens 5SU1324-6FA10 SENTRON RCBO, 2P, 10 A, B Curve, 10 kA","metaDescription":"Siemens SENTRON 5SU1324-6FA10 RCBO, 2-pole, 10 A rated, B tripping curve, 10 kA (EN 60898) / 20 kA (IEC 60947-2). Current production. Quoted to order against RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Residual Current Breakers (RCCB/RCBO)"],"specifications":{"Depth":"77 mm","Width":"54 mm","Height":"90 mm","Maximum":"75 °C","Minimum":"-40 °C","Halogen-Free":"Yes","Silicon-Free":"Yes","Design Of Pole":"2P","Number Of Poles":"2","lifecycle_stage":"current","Mounting Position":"any","at AC rated value":"230/240 V","Installation Depth":"70 mm","Product Brand Name":"SENTRON","Degree Of Pollution":"2","Operating Frequency":"50 Hz","Product Designation":"RCBO","protection class IP":"IP20, if the distribution board is installed, with connected conductors","Overvoltage Category":"III","Design Of The Product":"Instantaneous","Weight With Packaging":"409 g","at 30 °C rated value":"10 A","at 40 °C rated value":"9.5 A","at 45 °C rated value":"9.3 A","at 50 °C rated value":"9 A","at 55 °C rated value":"8.7 A","at 60 °C rated value":"8.5 A","at 65 °C rated value":"8.1 A","at 70 °C rated value":"7.7 A","Energy Limitation Class":"3","For Testing Equipment Minimum":"195 V","Number Of Modular Width Units":"3","Position Of Power Supply Cord":"Either top or bottom","Tripping Characteristic Class":"B","Number Of Poles With Protection":"2","according to EN 60898 rated value":"10 kA","insulation voltage (Ui) rated value":"264 V","Supply Voltage Frequency Rated Value":"50 Hz","Surge Voltage Resistance Rated Value":"4 000 V","according to IEC 60947-2 rated value":"20 kA","Surge Current Resistance At (8/20) μS":"1 kA","Influence Of The Surrounding Temperature":"Max. 95% humidity","Type Of Voltage Of The Operating Voltage":"AC","Mechanical Service Life (Operating Cycles) Typical":"10 000"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":"$55.88","priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/f8a3f804604e34cc21a3fa836405929c.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=134322&mlfb=5SU1324-6FA10","alternativesUrl":"https://aoctrl.com/api/mcp/products/5SU1324-6FA10/alternatives.json"},"ai":{"faq":[],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/5SU1324-6FA10","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/5SU1324-6FA10 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}