{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"5SU1324-6FP10","brand":"Siemens","brandSlug":"siemens","productSlug":"5SU1324-6FP10","canonicalUrl":"https://aoctrl.com/siemens/5SU1324-6FP10","factsUrl":"https://aoctrl.com/api/mcp/products/5SU1324-6FP10","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON RCBO, 2-pole, 10 A, B-curve, 10 kA (EN 60898) / 15 kA (IEC 60947-2), 2 MW, IP20, -40 to 70 °C.","salesMarkdown":"It's not sized for motor starting; that wants a C or D curve. Either way, it clears a bolted fault without venting or welding contacts — that's the job. Temperature derating is built into the spec: 10 A at 30 °C ambient drops to 8.2 A at 70 °C. If this RCBO lives in a hot enclosure next to contactors or drives, use the 70 °C figure for the continuous load — not the 30 °C number. The operating range (-40 to 70 °C) covers outdoor cabinets in cold climates and warm panels alike. Two modular-width units (36 mm wide) snap onto standard DIN rail. Depth is 72 mm; installation depth 70 mm. Mount in any position — no derating for orientation. Supply can land top or bottom, which saves a few minutes if you're retrofitting into a crowded enclosure and the busbar comes in from the bottom. IP20 with conductors connected and the distribution board installed — that's the usual for a panelboard. Not for washdown or outdoor exposed mounting without an enclosure.","metaTitle":"Siemens 5SU1324-6FP10 SENTRON RCBO, 10 A B-curve, 10 kA","metaDescription":"Siemens 5SU1324-6FP10 SENTRON RCBO, 2-pole, 10 A, B-curve, 10 kA (EN 60898) / 15 kA (IEC 60947-2). Active production, sourced to order. Quoted on request.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Residual Current Breakers (RCCB/RCBO)"],"specifications":{"Depth":"72 mm","Width":"36 mm","Height":"85 mm","Maximum":"70 °C","Minimum":"-40 °C","Halogen-Free":"No","Design Of Pole":"2P","Number Of Poles":"2","lifecycle_stage":"current","Mounting Position":"any","at AC rated value":"230/240 V","Installation Depth":"70 mm","Product Brand Name":"SENTRON","Degree Of Pollution":"3","Operating Frequency":"50 Hz","Product Designation":"RCBO","protection class IP":"IP20, if the distribution board is installed, with connected conductors","Overvoltage Category":"III","Design Of The Product":"Instantaneous","Weight With Packaging":"248 g","at 30 °C rated value":"10 A","at 40 °C rated value":"9.6 A","at 45 °C rated value":"9.4 A","at 50 °C rated value":"9.1 A","at 55 °C rated value":"8.9 A","at 60 °C rated value":"8.6 A","at 70 °C rated value":"8.2 A","Energy Limitation Class":"3","For Testing Equipment Minimum":"195 V","Number Of Modular Width Units":"2","Position Of Power Supply Cord":"Either top or bottom","Tripping Characteristic Class":"B","Number Of Poles With Protection":"2","according to EN 60898 rated value":"10 kA","insulation voltage (Ui) rated value":"500 V","Supply Voltage Frequency Rated Value":"50 Hz","Surge Voltage Resistance Rated Value":"4 000 V","according to IEC 60947-2 rated value":"15 kA","Surge Current Resistance At (8/20) μS":"0.25 kA","Influence Of The Surrounding Temperature":"Max. 95% humidity","Type Of Voltage Of The Operating Voltage":"AC","Mechanical Service Life (Operating Cycles) Typical":"10 000","for rated value of the current at AC in hot operating state per pole":"1.03 W"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/f8a3f804604e34cc21a3fa836405929c.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=1108766&mlfb=5SU1324-6FP10","alternativesUrl":"https://aoctrl.com/api/mcp/products/5SU1324-6FP10/alternatives.json"},"ai":{"faq":[{"question":"Where can I buy the 5SU1324-6FP10?","answer":"The 5SU1324-6FP10 is sourced to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time."},{"question":"What is the breaking capacity of the 5SU1324-6FP10?","answer":"10 kA per EN 60898 and 15 kA per IEC 60947-2. The higher IEC figure applies in industrial panels where fault current may exceed the residential standard."},{"question":"Will the 5SU1324-6FP10 drop into a panel specified around a 5SY4310-7CV?","answer":"Both are 2-pole RCBOs with a 10 A B-curve rating, but the 5SY4310-7CV is a different series with different breaking capacities and dimensions. The 5SU1324-6FP10 is a 2 MW unit with 10 kA/15 kA breaking capacity; verify physical fit and coordination before substituting."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/5SU1324-6FP10","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/5SU1324-6FP10 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}