{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"5SU1324-6FR16","brand":"Siemens","brandSlug":"siemens","productSlug":"5SU1324-6FR16","canonicalUrl":"https://aoctrl.com/siemens/5SU1324-6FR16","factsUrl":"https://aoctrl.com/api/mcp/products/5SU1324-6FR16","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON RCBO, 5SU1324-6FR16, 2-pole, B-curve, 16 A, 30 mA, Type A, 10 kA (EN 60898).","salesMarkdown":"Rated breaking capacity is 10 kA per EN 60898 and 15 kA per IEC 60947-2, putting it in the standard residential and light commercial range for a 16 A RCBO. The higher IEC rating gives headroom for industrial panels where fault levels may exceed the EN threshold. ## Temperature derating and mounting Rated 16 A at 30 °C; derates to 15.2 A at 40 °C and 13.4 A at 60 °C. In a warm enclosure the continuous load must stay under the derated value to avoid nuisance tripping. Touch protection is integrated on the terminals.","metaTitle":"Siemens SENTRON 5SU1324-6FR16 RCBO, 2-pole, B-curve, 16 A, 3","metaDescription":"Siemens SENTRON 5SU1324-6FR16 RCBO, 2-pole, Type A, B-curve, 16 A, 30 mA. Rated 10 kA (EN 60898) / 15 kA (IEC 60947-2). Current production. Sourced to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Residual Current Breakers (RCCB/RCBO)"],"specifications":{"Depth":"72 mm","Width":"36 mm","Height":"85 mm","Maximum":"70 °C","Minimum":"-40 °C","Halogen-Free":"No","Number Of Poles":"2","lifecycle_stage":"current","Mounting Position":"Any","Installation Depth":"70 mm","Product Brand Name":"SENTRON","Degree Of Pollution":"3","Operating Frequency":"50/60 Hz","Product Designation":"RCBO","acc. to IEC 81346-2":"F","at AC / rated value":"16 A","protection class IP":"IP20, if the distribution board is installed, with connected conductors","Overvoltage Category":"III","Design Of The Product":"Super resistant K","Residual Current Type":"A","acc. to DIN EN 61346-2":"F","Energy Limitation Class":"3","Weight / With Packaging":"265 g","at 30 °C / rated value":"16 A","at 40 °C / rated value":"15.2 A","at 45 °C / rated value":"14.8 A","at 50 °C / rated value":"14.3 A","at 55 °C / rated value":"13.9 A","at 60 °C / rated value":"13.4 A","Number Of Modular Width Units":"2","Tripping Characteristic Class":"B","acc. to EN 60898 / rated value":"10 kA","For Testing Equipment / Minimum":"195 V","Position / Of Power Supply Cord":"Either top or bottom","Number Of Poles / With Protection":"2","acc. to IEC 60947-2 / rated value":"15 kA","Product Feature / Touch Protection":"Yes","Tripping Fault Current / Rated Value":"30 mA","insulation voltage (Ui) / rated value":"500 V","Supply Voltage Frequency / Rated Value":"50 Hz","Surge Voltage Resistance / Rated Value":"4 000 V","Influence Of The Surrounding Temperature":"Max. 95% humidity","Surge Current Resistance / At (8/20) μS":"3 kA","Type Of Voltage / Of The Operating Voltage":"AC","Product Component / Neutral Conductor Switching":"Yes","Mechanical Service Life (Switching Cycles) / Typical":"10 000"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/f8a3f804604e34cc21a3fa836405929c.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=1108773&mlfb=5SU1324-6FR16","alternativesUrl":"https://aoctrl.com/api/mcp/products/5SU1324-6FR16/alternatives.json"},"ai":{"faq":[{"question":"What is the breaking capacity of 5SU1324-6FR16?","answer":"10 kA per EN 60898 and 15 kA per IEC 60947-2. The higher IEC figure applies when the device is certified to that standard for industrial applications."},{"question":"What does the 30 mA Type A residual current rating mean?","answer":"Type A detects sinusoidal AC fault currents plus pulsating DC fault currents, covering most modern electronic loads that generate half-wave rectified leakage. The 30 mA threshold provides additional protection against fatal electric shock."},{"question":"Where can I buy the 5SU1324-6FR16?","answer":"Sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/5SU1324-6FR16","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/5SU1324-6FR16 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}