{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"5SU1324-6KK82","brand":"Siemens","brandSlug":"siemens","productSlug":"5SU1324-6KK82","canonicalUrl":"https://aoctrl.com/siemens/5SU1324-6KK82","factsUrl":"https://aoctrl.com/api/mcp/products/5SU1324-6KK82","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON RCBO, 2-pole (2P), B-curve, 10 kA per EN 60898 / IEC 60947-2, 30 mA Type A residual current, rated 125 A at 30 °C, 77 x 117 x 90 mm.","salesMarkdown":"The Siemens SENTRON 5SU1324-6KK82 is a 2-pole (2P) RCBO — a combined overcurrent and residual-current device — rated 125 A at 30 °C with a B-curve trip characteristic and 30 mA Type A residual current protection. The 125 A rating at 30 °C is the headline number, but the derated values matter more for a warm enclosure: at 40 °C it carries 115.62 A, at 50 °C it drops to 106.25 A, and at 60 °C it's 96.25 A. If your panel ambient runs 45 °C, plan for 111.25 A continuous — not the full 125 A. For motor or transformer circuits with higher inrush, a C-curve sibling would be the usual pick. Type A residual current detection means it catches both sinusoidal AC faults and pulsating DC faults — the kind a single-phase rectifier load (switched-mode supply, LED driver, washing machine) can produce. That covers most modern final circuits; Type AC would miss the pulsating component. Rated 50 Hz only — not 50/60 Hz. If the installation is on a 60 Hz supply (North America, parts of South America and Japan), this RCBO is not the correct fit. Pollution degree 2 is the normal indoor-panel condition. The 77 mm depth and 117 mm width (7 modular width units) fit a standard distribution board cutout. Installation depth is 70 mm — the rail-to-front-panel clearance needed. Supply can enter from either top or bottom; mounting position is any orientation. IP20 with the distribution board installed and conductors connected — normal for an enclosed panel. Touch protection is built into the terminals. Halogen-free and silicon-free construction, which matters for clean-room or semiconductor-adjacent installations where outgassing can contaminate optics or sensitive surfaces.","metaTitle":"Siemens SENTRON 5SU1324-6KK82 RCBO, 2P, B-10kA, 30mA, 125A","metaDescription":"Siemens SENTRON 5SU1324-6KK82 RCBO, 2-pole, B-curve, 10 kA breaking capacity, 30 mA Type A RCD, rated 125 A. Current production. Quoted to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":[],"specifications":{"Depth":"77 mm","Poles":"2","Width":"117 mm","Height":"90 mm","Product Status":"Active","Energy Limitation Class":"3"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/f8a3f804604e34cc21a3fa836405929c.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=126207&mlfb=5SU1324-6KK82","alternativesUrl":"https://aoctrl.com/api/mcp/products/5SU1324-6KK82/alternatives.json"},"ai":{"faq":[],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/5SU1324-6KK82","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/5SU1324-6KK82 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}