{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"5SU1324-6KX06","brand":"Siemens","brandSlug":"siemens","productSlug":"5SU1324-6KX06","canonicalUrl":"https://aoctrl.com/siemens/5SU1324-6KX06","factsUrl":"https://aoctrl.com/api/mcp/products/5SU1324-6KX06","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 5SU1324-6KX06 RCBO, 2-pole, B-curve, 6 A rated, 30 mA residual current, 10 kA breaking capacity per EN 60898, 35 kA per IEC 60947-2, 110/120 V AC, 3 MW, IP20.","salesMarkdown":"The Siemens 5SU1324-6KX06 is a 2-pole residual current operated circuit breaker (RCBO) from the SENTRON series, combining overcurrent protection and 30 mA residual current detection in a single 3-module-width unit (54 mm wide per, 90 mm tall per, 77 mm deep per). The 30 mA residual sensitivity covers personnel protection (indirect contact) and fire prevention per IEC 60364. The 4 000 V surge voltage resistance and overvoltage category III confirm it is rated for fixed-installation mains supply, not downstream equipment-level protection. Mounts on DIN rail in any orientation. The 70 mm installation depth plus 7 mm for the housing means it clears most 80 mm deep enclosures. IP20 rating applies only when the distribution board is installed and conductors are connected — this is a panel-internal device, not surface-mount. The 95% humidity limit is standard for enclosed electrical rooms.","metaTitle":"Siemens 5SU1324-6KX06 SENTRON RCBO, 6A B-curve 30mA 2P 10kA","metaDescription":"Siemens 5SU1324-6KX06 SENTRON RCBO, 6 A rated, B-curve, 30 mA residual, 2-pole, 10 kA (EN 60898) / 35 kA (IEC 60947-2). Active production. Quoted to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Residual Current Breakers (RCCB/RCBO)"],"specifications":{"Depth":"77 mm","Width":"54 mm","Height":"90 mm","Maximum":"75 °C","Minimum":"-40 °C","Halogen-Free":"Yes","Silicon-Free":"Yes","Design Of Pole":"2P","Number Of Poles":"2","lifecycle_stage":"current","Mounting Position":"any","at AC rated value":"110/120 V","Installation Depth":"70 mm","Product Brand Name":"SENTRON","Degree Of Pollution":"2","Operating Frequency":"50/60 Hz","Product Designation":"RCBO","protection class IP":"IP20, if the distribution board is installed, with connected conductors","Overvoltage Category":"III","Design Of The Product":"Instantaneous","Weight With Packaging":"424 g","Energy Limitation Class":"3","For Testing Equipment Minimum":"100 V","Number Of Modular Width Units":"3","Position Of Power Supply Cord":"Either top or bottom","Tripping Characteristic Class":"B","Number Of Poles With Protection":"2","according to EN 60898 rated value":"10 kA","insulation voltage (Ui) rated value":"264 V","Supply Voltage Frequency Rated Value":"50 Hz","Surge Voltage Resistance Rated Value":"4 000 V","according to IEC 60947-2 rated value":"35 kA","Surge Current Resistance At (8/20) μS":"1 kA","Influence Of The Surrounding Temperature":"Max. 95% humidity","Type Of Voltage Of The Operating Voltage":"AC","Mechanical Service Life (Operating Cycles) Typical":"10 000"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/f8a3f804604e34cc21a3fa836405929c.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=603546&mlfb=5SU1324-6KX06","alternativesUrl":"https://aoctrl.com/api/mcp/products/5SU1324-6KX06/alternatives.json"},"ai":{"faq":[{"question":"How do I get current pricing and availability for 5SU1324-6KX06?","answer":"Submit an RFQ against this order code. Pricing and stock are confirmed at quote time through independent distribution channels — no automated price or lead-time figure is published here."},{"question":"Will 5SU1324-6KX06 drop into a panel specified around 5SU9354-7KK16 without rewiring?","answer":"No — the 5SU1324-6KX06 is a 2-pole RCBO (54 mm wide, 3 MW) while the 5SU9354-7KK16 is a 1P+N RCBO (36 mm wide, 2 MW) with a C-curve at 230/240 V. The pole count, voltage rating, and trip characteristic differ; the panel busbar and wiring would need reconfiguration."},{"question":"What compliance documentation does Siemens provide for 5SU1324-6KX06?","answer":"The RCBO carries ratings per EN 60898 (10 kA) and IEC 60947-2 (35 kA). It is halogen-free and silicon-free. Standard Siemens declarations for RoHS and REACH are available on request with the order documentation."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/5SU1324-6KX06","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/5SU1324-6KX06 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}