{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"5SU1324-7FA06","brand":"Siemens","brandSlug":"siemens","productSlug":"5SU1324-7FA06","canonicalUrl":"https://aoctrl.com/siemens/5SU1324-7FA06","factsUrl":"https://aoctrl.com/api/mcp/products/5SU1324-7FA06","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON RCBO, 2-pole, C-curve 6 A, 10 kA per EN 60898 / 35 kA per IEC 60947-2, 230/240 V AC, 50 Hz, IP20.","salesMarkdown":"It combines earth-leakage detection and overcurrent tripping in a single 3-module-width unit, saving a DIN-rail slot compared to separate RCCB + MCB. The thermal derating curve is published: 5.7 A at 40 °C, stepping down to 4.62 A at 70 °C — factor that into your panel ambient if it sits near heat sources. Snaps onto standard 35 mm DIN rail. 54 mm wide (3 module units), 77 mm deep, 90 mm tall. Supply can enter from top or bottom — no orientation restriction. IP20 with the distribution board closed and conductors connected; install inside a rated enclosure. Overvoltage category III, pollution degree 2 — suitable for fixed-installation panelboards downstream of the service entrance. Insulation voltage rated 264 V, surge withstand 4 kV. Listed as current production. No end-of-life notice or successor assigned.","metaTitle":"Siemens 5SU1324-7FA06 SENTRON RCBO, 2P C6, 10kA/35kA","metaDescription":"Siemens SENTRON 5SU1324-7FA06 RCBO, 2-pole, C-curve 6A, 10 kA (EN 60898) / 35 kA (IEC 60947-2). Current production. Sourced to order against RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Residual Current Breakers (RCCB/RCBO)"],"specifications":{"Depth":"77 mm","Width":"54 mm","Height":"90 mm","Maximum":"75 °C","Minimum":"-40 °C","Halogen-Free":"Yes","Silicon-Free":"Yes","Design Of Pole":"2P","Number Of Poles":"2","lifecycle_stage":"current","Mounting Position":"any","at AC rated value":"230/240 V","Installation Depth":"70 mm","Product Brand Name":"SENTRON","Degree Of Pollution":"2","Operating Frequency":"50 Hz","Product Designation":"RCBO","protection class IP":"IP20, if the distribution board is installed, with connected conductors","Overvoltage Category":"III","Design Of The Product":"Instantaneous","Weight With Packaging":"410 g","at 30 °C rated value":"6 A","at 40 °C rated value":"5.7 A","at 45 °C rated value":"5.58 A","at 50 °C rated value":"5.4 A","at 55 °C rated value":"5.22 A","at 60 °C rated value":"5.1 A","at 65 °C rated value":"4.86 A","at 70 °C rated value":"4.62 A","Energy Limitation Class":"3","For Testing Equipment Minimum":"195 V","Number Of Modular Width Units":"3","Position Of Power Supply Cord":"Either top or bottom","Tripping Characteristic Class":"C","Number Of Poles With Protection":"2","according to EN 60898 rated value":"10 kA","insulation voltage (Ui) rated value":"264 V","Supply Voltage Frequency Rated Value":"50 Hz","Surge Voltage Resistance Rated Value":"4 000 V","according to IEC 60947-2 rated value":"35 kA","Surge Current Resistance At (8/20) μS":"1 kA","Influence Of The Surrounding Temperature":"Max. 95% humidity","Type Of Voltage Of The Operating Voltage":"AC","Mechanical Service Life (Operating Cycles) Typical":"10 000"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/f8a3f804604e34cc21a3fa836405929c.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=90408&mlfb=5SU1324-7FA06","alternativesUrl":"https://aoctrl.com/api/mcp/products/5SU1324-7FA06/alternatives.json"},"ai":{"faq":[{"question":"Where can I buy 5SU1324-7FA06 and get a price?","answer":"This part is sourced and quoted to order against an RFQ through independent distribution. Submit an RFQ for current pricing and availability — confirmed at quote time, not before."},{"question":"What is the breaking capacity of 5SU1324-7FA06?","answer":"10 kA per EN 60898 and 35 kA per IEC 60947-2. The higher figure applies when the RCBO is installed in an industrial distribution board per the manufacturer's instructions."},{"question":"What compliance documentation does Siemens provide for 5SU1324-7FA06?","answer":"The part is halogen-free and silicon-free. Standard Siemens declarations for RoHS and REACH are available on request; the product carries the CE mark for the European market."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/5SU1324-7FA06","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/5SU1324-7FA06 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}