{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"5SU1324-7FA32","brand":"Siemens","brandSlug":"siemens","productSlug":"5SU1324-7FA32","canonicalUrl":"https://aoctrl.com/siemens/5SU1324-7FA32","factsUrl":"https://aoctrl.com/api/mcp/products/5SU1324-7FA32","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 5SU1324-7FA32 RCBO, 2-pole, type A, 30 mA, C-characteristic, In: 32 A, Un AC: 230/240 V, 10 kA (EN 60898) / 15 kA (IEC 60947-2).","salesMarkdown":"## What this RCBO covers It combines a 32 A thermal-magnetic overcurrent trip (C-curve) with a 30 mA type A residual-current detection block in a single 3-module-width (54 mm) package. The 30 mA residual sensitivity covers basic shock protection for personnel. The 1 kA surge-current withstand (8/20 μs waveform) is the impulse-sparkover rating; it means the device survives typical lightning-induced transients without nuisance tripping or internal damage. ## Panel fit and environment Dimensions are 90 mm high, 54 mm wide (3 modular units), 77 mm deep, with a 70 mm installation depth. That 77 mm depth is the body-only; the 70 mm installation depth is what matters for enclosure selection — it fits standard 80 mm-deep distribution boards. IP20 rating applies only with the distribution board installed and conductors connected — not a standalone IP rating for open-panel use.","metaTitle":"Siemens 5SU1324-7FA32 SENTRON RCBO, 32A, 30mA, C-Curve, 2P","metaDescription":"Siemens 5SU1324-7FA32 SENTRON RCBO, 32A rated, 30mA residual, C-curve, 2-pole, 10kA (EN 60898) / 15kA (IEC 60947-2). Active production, sourced to order. Request quote.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Residual Current Breakers (RCCB/RCBO)"],"specifications":{"Depth":"77 mm","Width":"54 mm","Height":"90 mm","Maximum":"75 °C","Minimum":"-40 °C","Halogen-Free":"Yes","Silicon-Free":"Yes","Design Of Pole":"2P","Number Of Poles":"2","lifecycle_stage":"current","Mounting Position":"any","at AC rated value":"230/240 V","Installation Depth":"70 mm","Product Brand Name":"SENTRON","Degree Of Pollution":"2","Operating Frequency":"50 Hz","Product Designation":"RCBO","protection class IP":"IP20, if the distribution board is installed, with connected conductors","Overvoltage Category":"III","Design Of The Product":"Instantaneous","Weight With Packaging":"417 g","Energy Limitation Class":"3","For Testing Equipment Minimum":"195 V","Number Of Modular Width Units":"3","Position Of Power Supply Cord":"Either top or bottom","Tripping Characteristic Class":"C","Number Of Poles With Protection":"2","according to EN 60898 rated value":"10 kA","insulation voltage (Ui) rated value":"264 V","Supply Voltage Frequency Rated Value":"50 Hz","Surge Voltage Resistance Rated Value":"4 000 V","according to IEC 60947-2 rated value":"15 kA","Surge Current Resistance At (8/20) μS":"1 kA","Influence Of The Surrounding Temperature":"Max. 95% humidity","Type Of Voltage Of The Operating Voltage":"AC","Mechanical Service Life (Operating Cycles) Typical":"10 000"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/f8a3f804604e34cc21a3fa836405929c.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=507521&mlfb=5SU1324-7FA32","alternativesUrl":"https://aoctrl.com/api/mcp/products/5SU1324-7FA32/alternatives.json"},"ai":{"faq":[{"question":"What are the key ratings for 5SU1324-7FA32?","answer":"32 A rated current, 30 mA type A residual, C-curve trip characteristic, 2-pole, 230/240 V AC, 10 kA (EN 60898) / 15 kA (IEC 60947-2) breaking capacity."},{"question":"What is the depth of 5SU1324-7FA32?","answer":"Body depth is 77 mm; installation depth is 70 mm."},{"question":"Where can I buy 5SU1324-7FA32 and get current pricing?","answer":"Sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time — submit an RFQ for a firm commercial offer."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/5SU1324-7FA32","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/5SU1324-7FA32 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}