{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"5SU1324-7FP10","brand":"Siemens","brandSlug":"siemens","productSlug":"5SU1324-7FP10","canonicalUrl":"https://aoctrl.com/siemens/5SU1324-7FP10","factsUrl":"https://aoctrl.com/api/mcp/products/5SU1324-7FP10","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON RCBO, 5SU1324-7FP10, 2-pole, 10 A at 30 °C, C-curve, 10 kA per EN 60898, 15 kA per IEC 60947-2, 2 MW wide, IP20.","salesMarkdown":"At 30 °C ambient it is rated 10 A; derate linearly to 8.2 A at 70 °C. The 2-pole design protects both phase and neutral, with the supply cord position flexible — top or bottom feed. ## Integration notes Depth is 72 mm, height 85 mm — verify enclosure depth clearance before panel layout. The 2 MW width (36 mm) occupies two adjacent 18 mm slots. Supply can enter from top or bottom; no polarity restriction on the line/load side for the overcurrent function. The residual current detection circuit requires the neutral conductor to pass through the internal summation CT — standard for 2-pole RCBOs.","metaTitle":"Siemens 5SU1324-7FP10 SENTRON RCBO, 10A C-Curve, 2-Pole, 10k","metaDescription":"Siemens 5SU1324-7FP10 SENTRON RCBO, 10A rated at 30°C, C-curve trip, 2-pole, 10kA breaking capacity per EN 60898. Current-production part. Quoted to order against RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Residual Current Breakers (RCCB/RCBO)"],"specifications":{"Depth":"72 mm","Width":"36 mm","Height":"85 mm","Maximum":"70 °C","Minimum":"-40 °C","Halogen-Free":"No","Design Of Pole":"2P","Number Of Poles":"2","lifecycle_stage":"current","Mounting Position":"any","at AC rated value":"230/240 V","Installation Depth":"70 mm","Product Brand Name":"SENTRON","Degree Of Pollution":"3","Operating Frequency":"50 Hz","Product Designation":"RCBO","protection class IP":"IP20, if the distribution board is installed, with connected conductors","Overvoltage Category":"III","Design Of The Product":"Instantaneous","Weight With Packaging":"256 g","at 30 °C rated value":"10 A","at 40 °C rated value":"9.6 A","at 45 °C rated value":"9.4 A","at 50 °C rated value":"9.1 A","at 55 °C rated value":"8.9 A","at 60 °C rated value":"8.6 A","at 70 °C rated value":"8.2 A","Energy Limitation Class":"3","For Testing Equipment Minimum":"195 V","Number Of Modular Width Units":"2","Position Of Power Supply Cord":"Either top or bottom","Tripping Characteristic Class":"C","Number Of Poles With Protection":"2","according to EN 60898 rated value":"10 kA","insulation voltage (Ui) rated value":"500 V","Supply Voltage Frequency Rated Value":"50 Hz","Surge Voltage Resistance Rated Value":"4 000 V","according to IEC 60947-2 rated value":"15 kA","Surge Current Resistance At (8/20) μS":"0.25 kA","Influence Of The Surrounding Temperature":"Max. 95% humidity","Type Of Voltage Of The Operating Voltage":"AC","Mechanical Service Life (Operating Cycles) Typical":"10 000","for rated value of the current at AC in hot operating state per pole":"1.03 W"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/f8a3f804604e34cc21a3fa836405929c.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=1108779&mlfb=5SU1324-7FP10","alternativesUrl":"https://aoctrl.com/api/mcp/products/5SU1324-7FP10/alternatives.json"},"ai":{"faq":[{"question":"What is the breaking capacity of 5SU1324-7FP10?","answer":"10 kA per EN 60898 and 15 kA per IEC 60947-2. The higher IEC rating applies when the device is used under the conditions specified in that standard (typically for industrial applications with higher prospective fault current)."},{"question":"Where can I buy 5SU1324-7FP10 and how is it quoted?","answer":"Sourced and quoted to order against an RFQ through independent industrial-automation distribution. Availability and current pricing are confirmed at quote time — no stock count or price is published here."},{"question":"What is the difference between 5SU1324-7FP10 and 5SY7210-7CC?","answer":"The 5SY7210-7CC is a Siemens SENTRON MCB (overcurrent protection only), while the 5SU1324-7FP10 is an RCBO that adds residual-current protection. Both share the same 2 MW width and C-curve characteristic, but the RCBO requires a neutral connection for the RCD function. They are not drop-in substitutes without rewiring the neutral path."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/5SU1324-7FP10","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/5SU1324-7FP10 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}