{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"5SU1324-7FP13","brand":"Siemens","brandSlug":"siemens","productSlug":"5SU1324-7FP13","canonicalUrl":"https://aoctrl.com/siemens/5SU1324-7FP13","factsUrl":"https://aoctrl.com/api/mcp/products/5SU1324-7FP13","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 5SU1324-7FP13, RCBO, 2-pole, C-curve, 13 A rated at 30 °C, 10 kA (EN 60898) / 15 kA (IEC 60947-2), 230/240 V AC, 50 Hz.","salesMarkdown":"## What this RCBO does in the panel The Siemens 5SU1324-7FP13 is a 2-pole SENTRON RCBO — a combined residual-current and miniature circuit breaker — rated 13 A at 30 °C with a C-curve trip characteristic and 10 kA breaking capacity per EN 60898 (15 kA per IEC 60947-2). It protects a 230/240 V AC, 50 Hz single-phase circuit against overload, short-circuit, and earth leakage in one 36 mm-wide (2 MW) module. The 10 kA SCCR at 230/240 V covers most commercial and light-industrial distribution boards; the 15 kA IEC 60947-2 rating gives headroom for higher-fault installations where the utility transformer sits close. ## Thermal derating — the real-world rating The 13 A rating holds only at 30 °C ambient inside the distribution board. At 40 °C the continuous current drops to 12.2 A; at 50 °C to 11.2 A; at 60 °C to 10.3 A; and at 70 °C to 9.3 A. If your panel runs warm — typical for a crowded enclosure near solar inverters or drive cabinets — size the upstream load to the derated figure, not the 30 °C label. The IP20 rating applies only when installed inside a distribution board with connected conductors — this is an enclosed-panel device, not a standalone enclosure. Mounting position is unrestricted, so it fits vertical or horizontal busbars.","metaTitle":"Siemens 5SU1324-7FP13 SENTRON RCBO, 2P C-curve 10 kA, 13 A","metaDescription":"Siemens 5SU1324-7FP13 SENTRON RCBO, 2-pole, 13 A rated, C-curve, 10 kA breaking capacity per EN 60898. Current production. Quoted to order against RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Residual Current Breakers (RCCB/RCBO)"],"specifications":{"Depth":"72 mm","Width":"36 mm","Height":"85 mm","Maximum":"70 °C","Minimum":"-40 °C","Halogen-Free":"No","Design Of Pole":"2P","Number Of Poles":"2","lifecycle_stage":"current","Mounting Position":"any","at AC rated value":"230/240 V","Installation Depth":"70 mm","Product Brand Name":"SENTRON","Degree Of Pollution":"3","Operating Frequency":"50 Hz","Product Designation":"RCBO","protection class IP":"IP20, if the distribution board is installed, with connected conductors","Overvoltage Category":"III","Design Of The Product":"Instantaneous","Weight With Packaging":"260 g","at 30 °C rated value":"13 A","at 40 °C rated value":"12.2 A","at 45 °C rated value":"11.7 A","at 50 °C rated value":"11.2 A","at 55 °C rated value":"10.8 A","at 60 °C rated value":"10.3 A","at 70 °C rated value":"9.3 A","Energy Limitation Class":"3","For Testing Equipment Minimum":"195 V","Number Of Modular Width Units":"2","Position Of Power Supply Cord":"Either top or bottom","Tripping Characteristic Class":"C","Number Of Poles With Protection":"2","according to EN 60898 rated value":"10 kA","insulation voltage (Ui) rated value":"500 V","Supply Voltage Frequency Rated Value":"50 Hz","Surge Voltage Resistance Rated Value":"4 000 V","according to IEC 60947-2 rated value":"15 kA","Surge Current Resistance At (8/20) μS":"0.25 kA","Influence Of The Surrounding Temperature":"Max. 95% humidity","Type Of Voltage Of The Operating Voltage":"AC","Mechanical Service Life (Operating Cycles) Typical":"10 000","for rated value of the current at AC in hot operating state per pole":"1.23 W"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/f8a3f804604e34cc21a3fa836405929c.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=1108780&mlfb=5SU1324-7FP13","alternativesUrl":"https://aoctrl.com/api/mcp/products/5SU1324-7FP13/alternatives.json"},"ai":{"faq":[{"question":"What is the breaking capacity of 5SU1324-7FP13?","answer":"10 kA per EN 60898 and 15 kA per IEC 60947-2 at 230/240 V AC, 50 Hz. The IEC rating gives additional fault-current headroom for industrial distribution boards."},{"question":"Where can I buy 5SU1324-7FP13?","answer":"This RCBO is sourced and quoted to order against an RFQ through independent distribution channels. Availability and current pricing are confirmed at quote time."},{"question":"What is the difference between 5SU1324-7FP13 and 5SY7210-7CC?","answer":"The 5SY7210-7CC is a Siemens miniature circuit breaker (MCB) only — it provides overcurrent and short-circuit protection but no residual-current detection. The 5SU1324-7FP13 is an RCBO that combines both functions in the same 2-MW footprint. If your circuit requires earth-leakage protection, the RCBO is the correct choice; an MCB alone would need a separate RCD upstream."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/5SU1324-7FP13","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/5SU1324-7FP13 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}