{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"5SU1324-7FP25","brand":"Siemens","brandSlug":"siemens","productSlug":"5SU1324-7FP25","canonicalUrl":"https://aoctrl.com/siemens/5SU1324-7FP25","factsUrl":"https://aoctrl.com/api/mcp/products/5SU1324-7FP25","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON RCBO, 2-pole, 25 A rated, 30 mA residual current, Type A, C characteristic, 10 kA breaking capacity per EN 60898, 2 MW, IP20.","salesMarkdown":"## RCBO with Type A residual current and C characteristic It carries a 25 A rated current at 30 °C ambient and trips on residual fault currents of 30 mA, Type A — meaning it detects sinusoidal AC faults and pulsating DC fault currents up to 6 mA ripple, per IEC 60755. The thermal derating curve is published: 24 A at 40 °C, 23.5 A at 45 °C, 23 A at 50 °C, 22.5 A at 55 °C, and 22 A at 60 °C (–). ## Mounting and environmental ratings","metaTitle":"Siemens SENTRON 5SU1324-7FP25 RCBO, 25 A, 30 mA, Type A, C C","metaDescription":"Siemens SENTRON 5SU1324-7FP25 RCBO, 2-pole, 25 A rated, 30 mA residual current, Type A, C characteristic, 10 kA breaking capacity per EN 60898. Current lifecycle stage. Sourced to","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Residual Current Breakers (RCCB/RCBO)"],"specifications":{"Depth":"72 mm","Width":"36 mm","Height":"85 mm","Maximum":"70 °C","Minimum":"-40 °C","Halogen-Free":"No","Number Of Poles":"2","lifecycle_stage":"current","Mounting Position":"Any","Installation Depth":"70 mm","Product Brand Name":"SENTRON","Degree Of Pollution":"3","Operating Frequency":"50 Hz","Product Designation":"RCBO","at AC / rated value":"25 A","protection class IP":"IP20, if the distribution board is installed, with connected conductors","Overvoltage Category":"III","Design Of The Product":"Instantaneous","Residual Current Type":"A","Energy Limitation Class":"3","Weight / With Packaging":"262 g","according to EN 61346-2":"F","at 30 °C / rated value":"25 A","at 40 °C / rated value":"24 A","at 45 °C / rated value":"23.5 A","at 50 °C / rated value":"23 A","at 55 °C / rated value":"22.5 A","at 60 °C / rated value":"22 A","according to IEC 81346-2":"F","Number Of Modular Width Units":"2","Tripping Characteristic Class":"C","For Testing Equipment / Minimum":"195 V","Position / Of Power Supply Cord":"Either top or bottom","Number Of Poles / With Protection":"2","Product Feature / Touch Protection":"Yes","according to EN 60898 / rated value":"10 kA","Tripping Fault Current / Rated Value":"30 mA","insulation voltage (Ui) / rated value":"500 V","Supply Voltage Frequency / Rated Value":"50 Hz","Surge Voltage Resistance / Rated Value":"4 000 V","according to IEC 60947-2 / rated value":"15 kA","Influence Of The Surrounding Temperature":"Max. 95% humidity","Surge Current Resistance / At (8/20) μS":"0.25 kA","Type Of Voltage / Of The Operating Voltage":"AC","Product Component / Neutral Conductor Switching":"Yes","Mechanical Service Life (Switching Cycles) / Typical":"10 000"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/f8a3f804604e34cc21a3fa836405929c.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=1108783&mlfb=5SU1324-7FP25","alternativesUrl":"https://aoctrl.com/api/mcp/products/5SU1324-7FP25/alternatives.json"},"ai":{"faq":[{"question":"Where can I buy 5SU1324-7FP25 and how do I get a price?","answer":"The 5SU1324-7FP25 is sourced to order against an RFQ through independent distribution. Submit a request for quote (RFQ) to confirm current availability and pricing — no stock or price figures are published here."},{"question":"What is the residual current type and trip threshold on 5SU1324-7FP25?","answer":"It is Type A (detects sinusoidal AC and pulsating DC fault currents) with a rated residual tripping current of 30 mA."},{"question":"What breaking capacity does 5SU1324-7FP25 carry per EN 60898?","answer":"The rated breaking capacity is 10 kA per EN 60898, suitable for most residential and light commercial sub-distribution boards."},{"question":"What is the width and modular unit count of 5SU1324-7FP25?","answer":"Width is 36 mm, which corresponds to 2 modular width units (MW) for DIN-rail mounting."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/5SU1324-7FP25","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/5SU1324-7FP25 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}