{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"5SU1324-7FR06","brand":"Siemens","brandSlug":"siemens","productSlug":"5SU1324-7FR06","canonicalUrl":"https://aoctrl.com/siemens/5SU1324-7FR06","factsUrl":"https://aoctrl.com/api/mcp/products/5SU1324-7FR06","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 5SU1324-7FR06 RCBO, 2-pole, C-curve, 6 A rated at 30 °C, 10 kA breaking capacity per EN 60898, 15 kA per IEC 60947-2, 2 MW width, IP20 when installed.","salesMarkdown":"## RCBO for branch-circuit protection with residual-current monitoring The C-curve means magnetic trip occurs at 5–10× In (30–60 A for this 6 A unit), suited for circuits with moderate inrush — think lighting banks, socket outlets, or small motor starters where the starting surge won't exceed that window. The higher IEC figure gives fault-clearing headroom for industrial panel applications where prospective short-circuit current may exceed the domestic standard's limit. ## Thermal derating and mounting flexibility Rated current is 6 A at 30 °C ambient, derating linearly to 4.7 A at 70 °C. In a crowded enclosure with elevated internal temperature, size the load to the derated value — the 70 °C figure is the operating limit, not storage. The 72 mm depth fits standard 70 mm installation depth distribution boards; the 36 mm width occupies two modular units on the DIN rail. ## Surge withstand and pollution environment Rated surge voltage resistance is 4 000 V, with surge current withstand of 3 kA at 8/20 µs waveform — relevant for installations in overvoltage category III environments (fixed installations with transient overvoltages).","metaTitle":"Siemens 5SU1324-7FR06 SENTRON RCBO, 6 A C-Curve, 2-Pole, 10","metaDescription":"Siemens SENTRON 5SU1324-7FR06 RCBO, 6 A rated, C-curve, 2-pole, 10 kA per EN 60898, 15 kA per IEC 60947-2. Current production. Sourced to order. Request quote.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":[],"specifications":{"Depth":"72 mm","Poles":"2","Width":"36 mm","Height":"85 mm","Product Status":"Active","Energy Limitation Class":"3"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/f8a3f804604e34cc21a3fa836405929c.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=1108786&mlfb=5SU1324-7FR06","alternativesUrl":"https://aoctrl.com/api/mcp/products/5SU1324-7FR06/alternatives.json"},"ai":{"faq":[],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/5SU1324-7FR06","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/5SU1324-7FR06 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}