{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"5SU1324-7FR10","brand":"Siemens","brandSlug":"siemens","productSlug":"5SU1324-7FR10","canonicalUrl":"https://aoctrl.com/siemens/5SU1324-7FR10","factsUrl":"https://aoctrl.com/api/mcp/products/5SU1324-7FR10","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 5SU1324-7FR10 RCBO, 2-pole, 10 A rated, C tripping characteristic, 30 mA Type A residual current, 10 kA / 15 kA breaking capacity.","salesMarkdown":"The 30 mA Type A residual-current element catches sinusoidal AC faults plus pulsating DC faults (common from rectified loads like VFDs, LED drivers, or switching power supplies). ## Thermal derating — the real-world current At 40 °C it derates to 9.6 A, at 50 °C to 9.1 A, and at 60 °C to 8.6 A. The 5SU1324-7FR10 occupies 2 MW (36 mm) on a DIN rail, with a depth of 72 mm and height of 85 mm. Installation depth is 70 mm — account for that behind the gland plate. Touch protection is built in (finger-safe terminals). Supply can enter from top or bottom, which simplifies busbar routing in a crowded enclosure.","metaTitle":"Siemens SENTRON 5SU1324-7FR10 RCBO, 2-pole 10 A C-curve 30 m","metaDescription":"Siemens SENTRON 5SU1324-7FR10 RCBO, 2-pole, 10 A rated, C characteristic, 30 mA Type A residual current. Breaking capacity 10 kA (EN 60898) / 15 kA (IEC 60947-2). Current productio","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Residual Current Breakers (RCCB/RCBO)"],"specifications":{"Depth":"72 mm","Width":"36 mm","Height":"85 mm","Maximum":"70 °C","Minimum":"-40 °C","Halogen-Free":"No","Number Of Poles":"2","lifecycle_stage":"current","Mounting Position":"Any","Installation Depth":"70 mm","Product Brand Name":"SENTRON","Degree Of Pollution":"3","Operating Frequency":"50/60 Hz","Product Designation":"RCBO","acc. to IEC 81346-2":"F","at AC / rated value":"10 A","protection class IP":"IP20, if the distribution board is installed, with connected conductors","Overvoltage Category":"III","Design Of The Product":"Super resistant K","Residual Current Type":"A","acc. to DIN EN 61346-2":"F","Energy Limitation Class":"3","Weight / With Packaging":"266 g","at 30 °C / rated value":"10 A","at 40 °C / rated value":"9.6 A","at 45 °C / rated value":"9.4 A","at 50 °C / rated value":"9.1 A","at 55 °C / rated value":"8.9 A","at 60 °C / rated value":"8.6 A","Number Of Modular Width Units":"2","Tripping Characteristic Class":"C","acc. to EN 60898 / rated value":"10 kA","For Testing Equipment / Minimum":"195 V","Position / Of Power Supply Cord":"Either top or bottom","Number Of Poles / With Protection":"2","acc. to IEC 60947-2 / rated value":"15 kA","Product Feature / Touch Protection":"Yes","Tripping Fault Current / Rated Value":"30 mA","insulation voltage (Ui) / rated value":"500 V","Supply Voltage Frequency / Rated Value":"50 Hz","Surge Voltage Resistance / Rated Value":"4 000 V","Influence Of The Surrounding Temperature":"Max. 95% humidity","Surge Current Resistance / At (8/20) μS":"3 kA","Type Of Voltage / Of The Operating Voltage":"AC","Product Component / Neutral Conductor Switching":"Yes","Mechanical Service Life (Switching Cycles) / Typical":"10 000"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/f8a3f804604e34cc21a3fa836405929c.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=1108787&mlfb=5SU1324-7FR10","alternativesUrl":"https://aoctrl.com/api/mcp/products/5SU1324-7FR10/alternatives.json"},"ai":{"faq":[{"question":"What is 5SU1324-7FR10's listed depth (72 mm) on this component line?","answer":"The overall depth is 72 mm; installation depth (behind the panel face) is 70 mm."},{"question":"What is 5SU1324-7FR10's listed width (36 mm) on this component line?","answer":"Width is 36 mm, which corresponds to 2 modular-width units on a standard DIN-rail grid."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/5SU1324-7FR10","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/5SU1324-7FR10 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}