{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"5SU1324-7KX06","brand":"Siemens","brandSlug":"siemens","productSlug":"5SU1324-7KX06","canonicalUrl":"https://aoctrl.com/siemens/5SU1324-7KX06","factsUrl":"https://aoctrl.com/api/mcp/products/5SU1324-7KX06","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON RCBO, 2-pole, 6 A rated, C-curve tripping characteristic, 30 mA Type A residual current, 10 kA breaking capacity, 3 modular width units.","salesMarkdown":"It's rated 6 A at 30 °C, with a 30 mA residual fault trip threshold and a 10 kA breaking capacity per EN 60898 — so it protects a final subcircuit against both overload/short-circuit and earth leakage in one device, saving a DIN row in the panel. Type A residual current detection means it catches pulsating DC fault currents from rectified loads — think LED drivers, switched-mode power supplies, or single-phase VFDs — not just sinusoidal AC leakage. That's the deciding factor for modern panels where you'd otherwise need a separate Type A RCD upstream. ## Thermal derating and installation constraints At 40 °C it derates to 5.7 A, at 50 °C to 5.4 A, and at 60 °C to 5.1 A — so if the panel runs hot (say a packed cabinet near a process oven), size the upstream protective device for the derated value, not the label current. The 3-module-width footprint (54 mm wide, 77 mm deep, 90 mm tall) occupies three 18 mm positions on a standard DIN rail. IP20 applies once the distribution board is installed and conductors are connected — so it's for enclosed panels only, not a standalone outdoor enclosure.","metaTitle":"Siemens SENTRON 5SU1324-7KX06 RCBO, 6A C-curve, 30mA Type A","metaDescription":"Siemens SENTRON 5SU1324-7KX06 RCBO, 2-pole, 6A rated, C-curve, 30mA Type A residual current, 10kA breaking capacity. Current production. Available to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Residual Current Breakers (RCCB/RCBO)"],"specifications":{"Depth":"77 mm","Width":"54 mm","Height":"90 mm","Maximum":"75 °C","Minimum":"-40 °C","Halogen-Free":"Yes","Silicon-Free":"Yes","Design Of Pole":"2P","Number Of Poles":"2","lifecycle_stage":"current","Mounting Position":"any","Installation Depth":"70 mm","Product Brand Name":"SENTRON","Degree Of Pollution":"2","Operating Frequency":"50/60 Hz","Product Designation":"RCBO","at AC / rated value":"6 A","protection class IP":"IP20, if the distribution board is installed, with connected conductors","Overvoltage Category":"III","Design Of The Product":"Instantaneous","Residual Current Type":"A","Energy Limitation Class":"3","Weight / With Packaging":"410 g","according to EN 61346-2":"F","at 30 °C / rated value":"6 A","at 40 °C / rated value":"5.7 A","at 45 °C / rated value":"5.58 A","at 50 °C / rated value":"5.4 A","at 55 °C / rated value":"5.22 A","at 60 °C / rated value":"5.1 A","at 65 °C / rated value":"4.86 A","at 70 °C / rated value":"4.62 A","according to IEC 81346-2":"F","Number Of Modular Width Units":"3","Tripping Characteristic Class":"C","For Testing Equipment / Minimum":"100 V","Position / Of Power Supply Cord":"Either top or bottom","Number Of Poles / With Protection":"2","according to EN 60898 / rated value":"10 kA","Tripping Fault Current / Rated Value":"30 mA","insulation voltage (Ui) / rated value":"264 V","Supply Voltage Frequency / Rated Value":"50 Hz","Surge Voltage Resistance / Rated Value":"4 000 V","according to IEC 60947-2 / rated value":"35 kA","Influence Of The Surrounding Temperature":"Max. 95% humidity","Surge Current Resistance / At (8/20) μS":"1 kA","Type Of Voltage / Of The Operating Voltage":"AC","Mechanical Service Life (Switching Cycles) / Typical":"10 000"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/f8a3f804604e34cc21a3fa836405929c.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=603554&mlfb=5SU1324-7KX06","alternativesUrl":"https://aoctrl.com/api/mcp/products/5SU1324-7KX06/alternatives.json"},"ai":{"faq":[{"question":"Where can I buy 5SU1324-7KX06 and how do I get a price?","answer":"We source this part to order against an RFQ. Submit the order code and quantity, and we'll confirm availability and current pricing at quote time."},{"question":"What is the difference between 5SU1324-7KX06 and a standard MCB + RCD combination?","answer":"This RCBO integrates both overcurrent and residual current protection in one device, saving one DIN module width compared to a separate MCB and RCD. The Type A detection handles pulsating DC faults that a standard Type AC RCD would miss."},{"question":"What compliance documentation does this RCBO carry?","answer":"The product is designed to EN 60898 (breaking capacity 10 kA) and IEC 61346-2 / IEC 81346-2 (function code F). It is halogen-free and silicon-free. Standard Siemens SENTRON documentation includes CE declaration and RoHS/REACH compliance statements."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/5SU1324-7KX06","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/5SU1324-7KX06 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}