{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"5SU1326-6FP06","brand":"Siemens","brandSlug":"siemens","productSlug":"5SU1326-6FP06","canonicalUrl":"https://aoctrl.com/siemens/5SU1326-6FP06","factsUrl":"https://aoctrl.com/api/mcp/products/5SU1326-6FP06","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 5SU1326-6FP06 RCBO, 2-pole, 6 A rated, 30 mA residual current, B tripping characteristic, 6 kA breaking capacity per EN 60898, 2 MW wide.","salesMarkdown":"The Siemens 5SU1326-6FP06 is a 2-pole RCBO from the SENTRON line — a combined residual-current and overcurrent protective device rated at 6 A with a 30 mA residual trip threshold and a B tripping characteristic. It's a current-production part, so no lifecycle surprises on a BOM freeze. The 6 A rating at 30 °C is the headline current. Derate to 5.7 A at 40 °C, 5.3 A at 50 °C, and 5 A at 60 °C (–) — that's the curve to check if the panel ambient runs hot. The 30 mA residual is Type A, which catches pulsating DC fault currents from single-phase rectified loads — VFDs, LED drivers, switching supplies. ## Panel integration Snaps onto DIN rail — 2 modular widths (36 mm wide,). Depth is 72 mm, installation depth 70 mm. Mounting position any, supply feed from top or bottom. IP20 with distribution board installed and conductors connected — so it's an enclosed-panel device, not a standalone outdoor unit. Listed as current production. No end-of-life notice or successor code in the record.","metaTitle":"Siemens 5SU1326-6FP06 SENTRON RCBO, 6 A, 30 mA, B Curve, 2-P","metaDescription":"Siemens 5SU1326-6FP06 SENTRON RCBO, 6 A rated, 30 mA residual current, B tripping curve, 2-pole, 6 kA breaking capacity per EN 60898. Current production. Available to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Residual Current Breakers (RCCB/RCBO)"],"specifications":{"Depth":"72 mm","Width":"36 mm","title":"5SU1326-6FP06","Height":"85 mm","Maximum":"70 °C","Minimum":"-40 °C","description":"RCBO, 6 kA, 2P Type A, 30 mA, B-Char, In: 06A Un: 230V","Halogen-Free":"No","Number Of Poles":"2","lifecycle_stage":"current","Mounting Position":"Any","Installation Depth":"70 mm","Product Brand Name":"SENTRON","Degree Of Pollution":"3","Operating Frequency":"50 Hz","Product Designation":"RCBO","at AC / rated value":"6 A","protection class IP":"IP20, if the distribution board is installed, with connected conductors","Overvoltage Category":"III","Design Of The Product":"Instantaneous","Residual Current Type":"A","Energy Limitation Class":"3","Weight / With Packaging":"261 g","according to EN 61346-2":"F","at 30 °C / rated value":"6 A","at 40 °C / rated value":"5.7 A","at 45 °C / rated value":"5.5 A","at 50 °C / rated value":"5.3 A","at 55 °C / rated value":"5.1 A","at 60 °C / rated value":"5 A","according to IEC 81346-2":"F","Number Of Modular Width Units":"2","Tripping Characteristic Class":"B","For Testing Equipment / Minimum":"195 V","Position / Of Power Supply Cord":"Either top or bottom","Number Of Poles / With Protection":"2","Product Feature / Touch Protection":"Yes","according to EN 60898 / rated value":"6 kA","Tripping Fault Current / Rated Value":"30 mA","insulation voltage (Ui) / rated value":"500 V","Supply Voltage Frequency / Rated Value":"50 Hz","Surge Voltage Resistance / Rated Value":"4 000 V","according to IEC 60947-2 / rated value":"8 kA","Influence Of The Surrounding Temperature":"Max. 95% humidity","Surge Current Resistance / At (8/20) μS":"0.25 kA","Type Of Voltage / Of The Operating Voltage":"AC","Product Component / Neutral Conductor Switching":"Yes","Mechanical Service Life (Switching Cycles) / Typical":"10 000"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"stockQuantity":0,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/f8a3f804604e34cc21a3fa836405929c.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=1108792&mlfb=5SU1326-6FP06"},"ai":{"faq":[{"question":"Where can I buy 5SU1326-6FP06 and how do I get a price?","answer":"Sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time — submit an RFQ for a firm price and lead time."},{"question":"What is 5SU1326-6FP06's listed depth?","answer":"72 mm overall depth, with 70 mm installation depth. Width is 36 mm (2 MW,), height 85 mm."},{"question":"What compliance documentation does this brand provide for 5SU1326-6FP06?","answer":"The part carries EN 60898 rating for breaking capacity and is classified per EN 61346-2 and IEC 81346-2. It is a Siemens SENTRON device — standard documentation includes CE declaration of conformity and manufacturer's test certificates; specific RoHS/REACH/UL documentation should be confirmed at time of order."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"icboms-matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/5SU1326-6FP06","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/5SU1326-6FP06 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-08-11T15:51:03.652Z","lastPublished":"2026-08-11T15:51:03.652Z","indexable":true}}