{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"5SU1326-7FP06","brand":"Siemens","brandSlug":"siemens","productSlug":"5SU1326-7FP06","canonicalUrl":"https://aoctrl.com/siemens/5SU1326-7FP06","factsUrl":"https://aoctrl.com/api/mcp/products/5SU1326-7FP06","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON RCBO, 2-pole, C-curve, 6 A rated at 30 °C, 6 kA per EN 60898, 7.5 kA per IEC 60947-2, 2 MW width, IP20.","salesMarkdown":"The Siemens 5SU1326-7FP06 is a 2-pole RCBO from the SENTRON family, combining overcurrent protection and residual current detection in a single 36 mm wide module. It carries a C-curve trip characteristic and is rated 6 A at 30 °C, with a breaking capacity of 6 kA per EN 60898 and 7.5 kA per IEC 60947-2. The 6 kA per EN 60898 covers domestic/commercial fault levels; the 7.5 kA per IEC 60947-2 gives headroom for industrial panel coordination. ## Temperature derating — the real-world current rating Like all thermal-magnetic RCBOs, the 5SU1326-7FP06 derates with ambient temperature. At 30 °C it carries 6 A; at 40 °C it drops to 5.7 A; at 50 °C to 5.3 A; at 60 °C to 5 A; and at 70 °C to 4.7 A. If the panel runs hot — near a drive cabinet or in a sealed enclosure — size up or account for the reduced capacity. IP20 applies only when installed in the enclosure.","metaTitle":"Siemens 5SU1326-7FP06 SENTRON RCBO, 2P C-curve 6A, 6kA","metaDescription":"Siemens SENTRON 5SU1326-7FP06 RCBO, 2-pole, C-curve, 6A rated at 30°C, 6kA per EN 60898. Active production. Sourced to order against RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Residual Current Breakers (RCCB/RCBO)"],"specifications":{"Depth":"72 mm","Width":"36 mm","title":"5SU1326-7FP06","Height":"85 mm","Maximum":"70 °C","Minimum":"-40 °C","description":"RCBO, 6 kA, 2P Type A, 30 mA, C-Char, In: 06A Un: 230V","Halogen-Free":"No","Design Of Pole":"2P","Number Of Poles":"2","lifecycle_stage":"current","Mounting Position":"any","at AC rated value":"230/240 V","Installation Depth":"70 mm","Product Brand Name":"SENTRON","Degree Of Pollution":"3","Operating Frequency":"50 Hz","Product Designation":"RCBO","protection class IP":"IP20, if the distribution board is installed, with connected conductors","Overvoltage Category":"III","Design Of The Product":"Instantaneous","Weight With Packaging":"259 g","at 30 °C rated value":"6 A","at 40 °C rated value":"5.7 A","at 45 °C rated value":"5.5 A","at 50 °C rated value":"5.3 A","at 55 °C rated value":"5.1 A","at 60 °C rated value":"5 A","at 70 °C rated value":"4.7 A","Energy Limitation Class":"3","For Testing Equipment Minimum":"195 V","Number Of Modular Width Units":"2","Position Of Power Supply Cord":"Either top or bottom","Tripping Characteristic Class":"C","Number Of Poles With Protection":"2","according to EN 60898 rated value":"6 kA","insulation voltage (Ui) rated value":"500 V","Supply Voltage Frequency Rated Value":"50 Hz","Surge Voltage Resistance Rated Value":"4 000 V","according to IEC 60947-2 rated value":"7.5 kA","Surge Current Resistance At (8/20) μS":"0.25 kA","Influence Of The Surrounding Temperature":"Max. 95% humidity","Type Of Voltage Of The Operating Voltage":"AC","Mechanical Service Life (Operating Cycles) Typical":"10 000","for rated value of the current at AC in hot operating state per pole":"0.53 W"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"stockQuantity":0,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/f8a3f804604e34cc21a3fa836405929c.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=1108800&mlfb=5SU1326-7FP06"},"ai":{"faq":[{"question":"Will 5SU1326-7FP06 drop into a panel specified around 5SY7210-7CC without rewiring?","answer":"Both are 2-pole, 36 mm wide DIN-rail modules with top/bottom feed, so the physical fit is the same. The 5SU1326-7FP06 is an RCBO (overcurrent + residual current), while the 5SY7210-7CC is an MCB only — verify whether the circuit needs residual current protection before substituting."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"icboms-matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/5SU1326-7FP06","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/5SU1326-7FP06 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-08-11T15:51:03.652Z","lastPublished":"2026-08-11T15:51:03.652Z","indexable":true}}