{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"5SU1326-7FP10","brand":"Siemens","brandSlug":"siemens","productSlug":"5SU1326-7FP10","canonicalUrl":"https://aoctrl.com/siemens/5SU1326-7FP10","factsUrl":"https://aoctrl.com/api/mcp/products/5SU1326-7FP10","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 5SU1326-7FP10 RCBO, 2-pole, C-curve, 10 A (30 °C), 6 kA per EN 60898, 50 Hz, IP20.","salesMarkdown":"The Siemens SENTRON 5SU1326-7FP10 is a 2-pole RCBO (residual current circuit breaker with overcurrent protection) in a 2-module-wide (36 mm) housing, depth 72 mm, height 85 mm. It combines a C-curve MCB and an RCD in one unit, saving one module width over separate devices. Rated 10 A at 30 °C ambient, with a temperature derating curve down to 8.2 A at 70 °C. Breaking capacity is 6 kA per EN 60898 and 7.5 kA per IEC 60947-2. Operates at 50 Hz only (230/240 V AC rated voltage). Mounting position any. IP20 with conductors connected and distribution board installed. ## Integration notes Two-module width (36 mm) fits standard DIN-rail enclosures. Installation depth 70 mm. For 50 Hz supply only — not suitable for 60 Hz systems. Maximum 95% humidity. Halogen-free construction is not specified. Protection class IP20 requires the distribution board to be installed and conductors connected.","metaTitle":"Siemens SENTRON 5SU1326-7FP10 RCBO, 2P C-curve 10 A, 6 kA","metaDescription":"Siemens SENTRON 5SU1326-7FP10 RCBO, 2-pole, C-curve, 10 A rated at 30 °C, 6 kA per EN 60898. 50 Hz only, IP20. Current production. Sourced to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Residual Current Breakers (RCCB/RCBO)"],"specifications":{"Depth":"72 mm","Width":"36 mm","title":"5SU1326-7FP10","Height":"85 mm","Maximum":"70 °C","Minimum":"-40 °C","description":"RCBO, 6 kA, 2P Type A, 30 mA, C-Char, In: 10A Un: 230V","Halogen-Free":"No","Design Of Pole":"2P","Number Of Poles":"2","lifecycle_stage":"current","Mounting Position":"any","at AC rated value":"230/240 V","Installation Depth":"70 mm","Product Brand Name":"SENTRON","Degree Of Pollution":"3","Operating Frequency":"50 Hz","Product Designation":"RCBO","protection class IP":"IP20, if the distribution board is installed, with connected conductors","Overvoltage Category":"III","Design Of The Product":"Instantaneous","Weight With Packaging":"256 g","at 30 °C rated value":"10 A","at 40 °C rated value":"9.6 A","at 45 °C rated value":"9.4 A","at 50 °C rated value":"9.1 A","at 55 °C rated value":"8.9 A","at 60 °C rated value":"8.6 A","at 70 °C rated value":"8.2 A","Energy Limitation Class":"3","For Testing Equipment Minimum":"195 V","Number Of Modular Width Units":"2","Position Of Power Supply Cord":"Either top or bottom","Tripping Characteristic Class":"C","Number Of Poles With Protection":"2","according to EN 60898 rated value":"6 kA","insulation voltage (Ui) rated value":"500 V","Supply Voltage Frequency Rated Value":"50 Hz","Surge Voltage Resistance Rated Value":"4 000 V","according to IEC 60947-2 rated value":"7.5 kA","Surge Current Resistance At (8/20) μS":"0.25 kA","Influence Of The Surrounding Temperature":"Max. 95% humidity","Type Of Voltage Of The Operating Voltage":"AC","Mechanical Service Life (Operating Cycles) Typical":"10 000","for rated value of the current at AC in hot operating state per pole":"1.03 W"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":"$136.75","stockQuantity":0,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/f8a3f804604e34cc21a3fa836405929c.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=1108801&mlfb=5SU1326-7FP10"},"ai":{"faq":[{"question":"What are the key ratings of the 5SU1326-7FP10?","answer":"2-pole RCBO, C-curve, 10 A at 30 °C, 6 kA per EN 60898 / 7.5 kA per IEC 60947-2, 230/240 V AC, 50 Hz only. Insulation voltage 500 V, rated surge voltage 4 kV."},{"question":"Does the 5SU1326-7FP10 work on 60 Hz?","answer":"No, it is rated for 50 Hz only. Operating frequency is 50 Hz."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"icboms-matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/5SU1326-7FP10","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/5SU1326-7FP10 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-08-11T15:51:03.652Z","lastPublished":"2026-08-11T15:51:03.652Z","indexable":true}}