{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"5SU1336-6FP16","brand":"Siemens","brandSlug":"siemens","productSlug":"5SU1336-6FP16","canonicalUrl":"https://aoctrl.com/siemens/5SU1336-6FP16","factsUrl":"https://aoctrl.com/api/mcp/products/5SU1336-6FP16","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 5SU1336-6FP16 RCBO, 3-pole, 16 A rated at 30 °C, Type B tripping characteristic, 6 kA breaking capacity per EN 60898, 400 V AC, 50 Hz.","salesMarkdown":"## Siemens SENTRON 5SU1336-6FP16 RCBO — 3-Pole, 16 A, Type B, 6 kA The 400 V AC, 50 Hz rating and overvoltage category III cover standard mains supply conditions. Rated current derates with ambient temperature: 15.2 A at 40 °C, 14.8 A at 45 °C, 14.3 A at 50 °C, 13.9 A at 55 °C, 13.4 A at 60 °C, and 12.5 A at 70 °C. This derating curve matters when the RCBO is installed in a crowded enclosure where internal temperature rise is expected — the 16 A label applies only at 30 °C ambient. Height is 85 mm. Supply can enter from either the top or bottom, simplifying busbar and cable routing in the panel. Rated for 95% humidity (non-condensing). ## Electrical ratings and compliance Insulation voltage (Ui) is 500 V. Surge voltage resistance is 4 kV. Surge current withstand is 0.25 kA at 8/20 µs waveform. Energy limitation class 3 indicates the device limits let-through energy to a low level during fault clearing, which aids downstream coordination. The RCBO is designed for instantaneous operation — no intentional time delay. Tested at a minimum of 340 V for routine testing.","metaTitle":"Siemens 5SU1336-6FP16 SENTRON RCBO, 3P, 16A, Type B, 6kA","metaDescription":"Siemens SENTRON 5SU1336-6FP16 RCBO, 3-pole, 16A rated at 30°C, Type B tripping curve, 6kA breaking capacity per EN 60898. 400V AC, 50Hz, IP20. Sourced to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":[],"specifications":{"Depth":"72 mm","Poles":"3","Width":"54 mm","Height":"85 mm","Product Status":"Active","Energy Limitation Class":"3"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/979712c24c6b011dea3bce9765f5eebe.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=1438040&mlfb=5SU1336-6FP16","alternativesUrl":"https://aoctrl.com/api/mcp/products/5SU1336-6FP16/alternatives.json"},"ai":{"faq":[],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/5SU1336-6FP16","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/5SU1336-6FP16 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}