{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"5SU1336-7FP10","brand":"Siemens","brandSlug":"siemens","productSlug":"5SU1336-7FP10","canonicalUrl":"https://aoctrl.com/siemens/5SU1336-7FP10","factsUrl":"https://aoctrl.com/api/mcp/products/5SU1336-7FP10","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 5SU1336-7FP10 RCBO, 3-pole, 10 A, 30 mA, Type A, 6 kA, 3 MW, IP20.","salesMarkdown":"## Thermal derating and ambient limits Above that, the continuous current must be derated: 9.6 A at 40 °C, 9.4 A at 45 °C, 9.1 A at 50 °C, 8.9 A at 55 °C, and 8.6 A at 60 °C. ## Residual current and protection characteristics Type A residual current detection means it catches sinusoidal AC faults and pulsating DC faults up to 30 mA — the standard for circuits with single-phase electronics, switched-mode power supplies, or rectifier loads. All three poles are protected (3P design), and the supply can enter from top or bottom — no orientation constraint during wiring.","metaTitle":"Siemens 5SU1336-7FP10 SENTRON RCBO, 10 A, 30 mA, Type A, 6 k","metaDescription":"Siemens 5SU1336-7FP10 SENTRON RCBO, 3-pole, 10 A rated, 30 mA residual current, Type A, 6 kA breaking capacity. Current production. Sourced to order against RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Residual Current Breakers (RCCB/RCBO)"],"specifications":{"Depth":"72 mm","Width":"54 mm","Height":"85 mm","Maximum":"70 °C","Minimum":"-40 °C","Halogen-Free":"No","Design Of Pole":"3P","Number Of Poles":"3","lifecycle_stage":"current","Mounting Position":"any","at AC rated value":"10 A","Installation Depth":"70 mm","Product Brand Name":"SENTRON","Degree Of Pollution":"3","Operating Frequency":"50 Hz","Product Designation":"RCBO","protection class IP":"IP20, if the distribution board is installed, with connected conductors","Overvoltage Category":"III","Design Of The Product":"Instantaneous","Residual Current Type":"A","Weight With Packaging":"363 g","at 30 °C rated value":"10 A","at 40 °C rated value":"9.6 A","at 45 °C rated value":"9.4 A","at 50 °C rated value":"9.1 A","at 55 °C rated value":"8.9 A","at 60 °C rated value":"8.6 A","Energy Limitation Class":"3","For Testing Equipment Minimum":"340 V","Number Of Modular Width Units":"3","Position Of Power Supply Cord":"Either top or bottom","Tripping Characteristic Class":"C","Number Of Poles With Protection":"3","according to EN 60898 rated value":"6 kA","Tripping Fault Current Rated Value":"30 mA","insulation voltage (Ui) rated value":"500 V","Supply Voltage Frequency Rated Value":"50 Hz","Surge Voltage Resistance Rated Value":"4 000 V","according to IEC 60947-2 rated value":"6 kA","Surge Current Resistance At (8/20) μS":"0.25 kA","Influence Of The Surrounding Temperature":"Max. 95% humidity","Type Of Voltage Of The Operating Voltage":"AC","Mechanical Service Life (Operating Cycles) Typical":"10 000"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/3d5d037361e577cbd051d5a23a3a0563.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=1438045&mlfb=5SU1336-7FP10","alternativesUrl":"https://aoctrl.com/api/mcp/products/5SU1336-7FP10/alternatives.json"},"ai":{"faq":[{"question":"What is the 5SU1336-7FP10's breaking capacity?","answer":"The breaking capacity is 6 kA according to both EN 60898 and IEC 60947-2."},{"question":"What is the residual current rating and type?","answer":"The rated residual fault current is 30 mA, and the device is Type A, detecting both AC and pulsating DC faults."},{"question":"Where can I buy the 5SU1336-7FP10?","answer":"The part is sourced and quoted to order against an RFQ through independent distribution, with availability and current pricing confirmed at quote time."},{"question":"Will the 5SU1336-7FP10 drop into a panel specified around the 5SY4310-7CV?","answer":"The 5SU1336-7FP10 is an RCBO (combined RCD/MCB), while the 5SY4310-7CV is a standalone MCB. The 5SU1336-7FP10 occupies 3 MW (54 mm) versus 1 MW for a single-pole MCB, so it will not drop in without panel rework — it requires additional DIN-rail space and different wiring for the neutral."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/5SU1336-7FP10","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/5SU1336-7FP10 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}